Belden 29504 010, VFD-Kabel, 3-8 AWG TC + 1G TC, XLPE, geschirmt, schwarzer PVC-Mantel

SKU:Belden 29504 010
$2,262.00
● Auf Lager
Beschreibung
Belden 29504 010, VFD-Kabel, 3-8 AWG TC + 1G TC, XLPE-Isolierung, geschirmt, schwarzer PVC-Mantel
Belden 300 % geerdetes flexibles VFD-Kabel / 1000 V UL flexibles Motorversorgungskabel
3-8 AWG verseiltes (7x19x29) verzinntes Kupfer + 1-8 AWG TC Erdungsleiter
VPE-Isolierung, M4-Farbcode + PVC-isolierter Boden
Insgesamt Beldfoil® + 85% TC-Geflechtschutz + TC-Abflussdraht
Sonnen- und ölbeständiger PVC-Mantel
600/1000 V TC-ER, 90ºC Nass/Trocken
Spezifikationen
| Attribute | Value |
|---|---|
| Number of Conductors | 3 |
| Conductor size | 8 AWG |
| Conductor stranding | 7x19x29 |
| Conductor Material | TC - Tinned Copper |
| Earth/ground wires | Yes |
| Insulated ground | 1 x 8 AWG, 7x19x29, TC - Tinned Copper, Insulated Ground Wire |
| Uninsulated ground wire | 4 x 14 AWG, 41x40, TC - Tinned Copper, Segmented Ground Wire (4 Totaling 8 AWG) |
| Conductor insulation material | XLP, XLPO, XLPE (Thermoset) |
| Conductor insulation nominal thickness | 0.062 in (1.6 mm) |
| Conductor nominal insulation diameter | 0.278 in (7.06 mm) |
| Conductor color code | ICEA Chart M4 |
| Insulated ground insulation material | PVC - Polyvinyl Chloride |
| Insulated ground nominal thickness | 0.062 in (1.6 mm) |
| Insulated ground nominal insulation diameter | 0.278 in (7.06 mm) |
| Insulated ground color | Green/Yellow Stripe |
| Shielded | Shielded |
| Outer shield (tape) | Tri-Laminate (Alum+Poly+Alum), 100% coverage |
| Drainwire type | 14 AWG (41x30) TC |
| Outer shield (braid) | Tinned Copper (TC), 85% coverage |
| Nom. outer shield DCR | 0.6 Ohm/1000ft (2.0 Ohm/km) |
| Jacket Material | PVC - Polyvinyl Chloride |
| Jacket Color | Black |
| Jacket nominal thickness | 0.095 in (2.4 mm) |
| Overall cable diameter (nominal) | 0.901 in (22.9 mm) |
| Ripcord | Yes |
| Voltage range | 1KV |
| Nom. Conductor DCR (Conductor(s)) | 0.599 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 26 pF/ft (85 pF/m) |
| Nom. capacitance (Cond-to-Shield) | 47 pF/ft (150 pF/m) |
| Nom. capacitance cond-to-other (conds + Shield) | 47 pF/ft (150 pF/m) |
| Nom. characteristic impedence | 71 Ohm |
| Nom. inductance cond-grnd | 0.17 µH/ft |
| Nom. velocity of prop. | 55% |
| Max. current | 55 Amps per Conductor at 30ºC (per NEC) |
| Nom. conductor DCR (insulated ground) | 0.6795 Ohm/1000ft (2.229 Ohm/km) |
| Nom. conductor DCR (segmented ground wire) | 0.67 Ohm/1000ft (2.2 Ohm/km) |
| UL temperature | 90°C Dry, 90°C Wet |
| Operating temperature | -40°C To +90°C |
| Bend radius (stationary min.) | 10.8 in (274 mm) |
| Bend radius (installation min.) | 10.8 in (274 mm) |
| Max Pull Tension | 1011 lbs (458.6 kg) |
| Bulk cable weight | 564 lbs/1000ft |
| NEC / UL compliance | Article 336, TC-ER, WTTC, UL Flexible Motor Supply Cable |
| AWM compliance | AWM I/II A/B |
| CEC / C(UL) compliance | CIC, TC |
| ICEA compliance | S-95-658 |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, IEEE 1202 FT4 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | P-07-KA070003-MSHA |
| Sustainability | CA Prop 65 |
| Other Part Numbers | 29504 010, 29504 010100, 29504 010250, 29504 010500, 29504 0101000 |
| Priced Per | FT |
Dokumente
Abbildungen dienen nur als Referenz. Spezifikationen können sich ohne Vorankündigung ändern — prüfen Sie vor dem Kauf die Eignung für Ihre Anwendung. Die Herstellerdokumentation ist maßgeblich.
Brauchen Sie einen Zuschnitt, Mengenpreise oder ein Datenblatt?
Unser Team erstellt Angebote für individuelle Längen und Großbestellungen, meist am selben Tag.