Belden 29506 010, VFD-Kabel, 3-4 AWG TC + 1G TC, XLPE, geschirmt, schwarzer PVC-Mantel specifications
AttributeValue
Number of Conductors3
Conductor size4 AWG
Conductor stranding7x19x25
Conductor MaterialTC - Tinned Copper
Insulated ground1 x 4 AWG, 7x19x25, TC - Tinned Copper, insulated ground wire
Uninsulated ground wire4 x 10 AWG, 105x30, TC - Tinned Copper, segmented ground wire (4 totaling 4 AWG)
Ground wire insulation materialPVC - Polyvinyl Chloride
Ground wire color codeGreen/Yellow Stripe
Tape shield materialTri-Laminate (Alum+Poly+Alum)
Tape shield coverage100%
Drainwire type10 AWG (105x30) TC
Braid shield materialTinned Copper (TC)
Braid shield coverage86%
RipcordYes
Conductor insulation nominal thickness0.062 in (1.6 mm)
Conductor nominal insulation diameter0.367 in (9.32 mm)
Ground wire nominal thickness0.062 in (1.6 mm)
Ground wire nominal insulation diameter0.367 in (9.32 mm)
Outer jacket nominal thickness0.093 in (2.4 mm)
Overall cable diameter (nominal)1.113 in (28.27 mm)
Bulk cable weight1061 lbs/1000ft
Nom. Conductor DCR (Conductor(s))0.239 Ohm/1000ft
Nom. capacitance cond-to-cond32 pF/ft (100 pF/m)
Nom. capacitance cond-to-other (conds + Shield)60 pF/m (18 pF/ft)
Nom. characteristic impedence37 Ohm
Nom. inductance cond-grnd0.12 µH/ft
Nom. velocity of prop.55%
Max. current95 Amps per Conductor at 30ºC
Nom. conductor DCR (insulated ground)0.2689 Ohm/1000ft (0.8822 Ohm/km)
Nom. Conductor DCR (uninsulated ground wire)0.2689 Ohm/1000ft (0.8822 Ohm/km)
Nom. outer shield DCR0.21 Ohm/1000ft (0.69 Ohm/km)
Bend radius (stationary min.)13.4 in (340 mm)
Bend radius (installation min.)13.4 in (340 mm)
Max Pull Tension2420 lbs (1100 kg)
NEC / UL complianceArticle 336, TC-ER, WTTC, UL Flexible Motor Supply Cable
AWM complianceAWM I/II A/B
CEC / C(UL) complianceCIC, TC
ICEA complianceS-95-658
Flammability / reaction to fireUL 1685 UL Loading, FT4, IEEE 1202 FT4
European directive complianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC complianceChina RoHS II (GB/T 26572-2011)
Other standard compliance(s)P-07-KA070003-MSHA
SustainabilityCA Prop 65
Other Part Numbers29506 010, 29506 010100, 29506 010250, 29506 010500, 29506 0101000
Priced PerFT

Dokumente

Abbildungen dienen nur als Referenz. Spezifikationen können sich ohne Vorankündigung ändern — prüfen Sie vor dem Kauf die Eignung für Ihre Anwendung. Die Herstellerdokumentation ist maßgeblich.

Brauchen Sie einen Zuschnitt, Mengenpreise oder ein Datenblatt?

Unser Team erstellt Angebote für individuelle Längen und Großbestellungen, meist am selben Tag.