Kontakt1-800-975-3686
Ramcorp Wire & Cable

Belden 29530 010, VFD-Kabel, 3C-2/0 AWG + 3G-4 AWG, XLPE, geschirmt, schwarzer Mantel

Belden 29530

SKU:Belden 29530 010

$5,749.20

Auf Lager

Beschreibung

Spezifikationen

Belden 29530 010, VFD-Kabel, 3C-2/0 AWG + 3G-4 AWG, XLPE, geschirmt, schwarzer Mantel specifications
AttributeValue
Notes (conductors)Finely Stranded Tinned Copper optomized for VFD use
Earth/ground wiresYes
Number of ground wires3 Wire
Segmented ground wire3
Notes (grounds)Segmented grounds (3 totaling 2/0 AWG)
Insulation thickness (nom.)0.057 in (1.4 mm)
Insulation diameter (nom.)0.552 in (14.0 mm)
ShieldShielded
Shield TypeCopper tape
Outer shield typeHelical tape
Notes (shield)2 mil copper tape for crack resistance and high frequency noise conduction
ArmorNo
CompositeNo
Jacket thickness (nom.)0.083 in (2.1 mm)
Nom. diameter1.368 in (34.75 mm)
Overall cable diameter (nominal)1.368 in (34.75 mm)
Bulk cable weight2016 lbs/1000ft (3000 kg/km)
Voltage range1KV
Nom. Conductor DCR (Conductor(s))0.075 Ohm/1000ft (0.25 Ohm/km)
Nom. capacitance cond-to-cond30 pF/ft (98 pF/m)
Nom. capacitance cond-to-other (conds + Shield)56 pF/ft (180 pF/m)
Nom. characteristic impedence36 Ohm
Nom. inductance cond-grnd0.067 µH/ft
Nom. velocity of prop.55%
Max. current195 Amps per Conductor at 30ºC
Nom. conductor DCR (segmented ground wire)0.08 Ohm/1000ft (0.26 Ohm/km)
Nom. outer shield DCR0.06 Ohm/1000ft (0.20 Ohm/km)
UL temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C
Stationary min. bend radius16.4 in (417 mm)
Installation min. bend radius16.4 in (417 mm)
Max Pull Tension6607 lbs (2997 kg)
Flammability / reaction to fireUL 1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL complianceArticle 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) complianceTC
ICEA complianceS-95-658
European directive complianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC complianceChina RoHS II (GB/T 26572-2011)
Other standard compliance(s)P-07-KA070003-MSHA
SustainabilityCA Prop 65
Other Part Numbers29530 010, 29530 010100, 29530 010250, 29530 010500, 29530 0101000, UPC 612825138068
Priced PerFT

Dokumente

Abbildungen dienen nur als Referenz. Spezifikationen können sich ohne Vorankündigung ändern — prüfen Sie vor dem Kauf die Eignung für Ihre Anwendung. Die Herstellerdokumentation ist maßgeblich.

Brauchen Sie einen Zuschnitt, Mengenpreise oder ein Datenblatt?

Unser Team erstellt Angebote für individuelle Längen und Großbestellungen, meist am selben Tag.