Belden 5100UE 008, Multi Conductor 2C 14 AWG FRPVC Gray

SKU:Belden 5100UE 008
● Auf Lager
Beschreibung
Belden 5100UE 008 is a security & commercial audio cable for indoor riser installations, designed for intercom/PA systems, sound/audio systems, and Fire Alarm applications (for color Red only)(Dual Rated). It features 2 14 AWG stranded bare copper conductors with polypropylene insulation and a PVC jacket with ripcord. The cable meets Riser-CL3R-FPLR requirements and carries a 300 V (CL3R, FPLR) UL voltage rating. Sequential footage marking every two feet helps support efficient pulls and accurate cut lengths.
Key Features
- 2 14 AWG stranded bare copper conductors (19x26) for security & commercial audio wiring.
- PP - Polypropylene insulation with black, white color code.
- PVC - Polyvinyl Chloride jacket with ripcord for easier stripping.
- UL voltage rating: 300 V (CL3R, FPLR).
- Sequential footage marking every two feet for cut-length accuracy.
Technical Specs
Construction & Materials
| Number of conductors | 2 |
|---|---|
| Conductor size | 14 AWG |
| Stranding | 19x26 |
| Conductor material | BC - Bare Copper |
| Insulation material | PP - Polypropylene |
| Nom. thickness | 0.011 in (0.28 mm) |
| Nom. insulation diameter | 0.092 in (2.3 mm) |
| Color code | Black, White |
| Jacket material | PVC - Polyvinyl Chloride |
| Ripcord | Yes |
| Nom. jacket thickness | 0.017 in (0.43 mm) |
| Nom. diameter | 0.218 in (5.54 mm) |
| Overall cable diameter (nominal) | 0.218 in (5.54 mm) |
| Plenum number | 6100UH |
Electrical Characteristics
| Nom. conductor DCR | 2.53 Ohm/1000ft |
|---|---|
| Nom. capacitance cond-to-cond | 22 pF/ft (72 pF/m) |
| Nom. inductance | 0.15 μH/ft (0.49 μH/m) |
| Max. current | 25 Amps per Conductor @ 30°C |
Environmental & Mechanical Ratings
| Operating | -20°C to +75°C |
|---|---|
| UL temperature | 75°C |
| Bend radius (stationary min.) | 2.2 in (56 mm) |
| Bend radius (installation min.) | 2.2 in (56 mm) |
| Max. pull tension | 95 lbs (43 kg) |
| Bulk cable weight | 33 lbs/1000ft |
| Environmental suitability | Indoor - Riser, Indoor |
Compliance & Certifications
| NEC / UL compliance | Article 725, Article 760, CL3R, FPLR |
|---|---|
| Flammability / reaction to fire | UL 1666 Riser, IEEE 1202 FT4, IEC 60332-1-2 |
| CPR Euroclass | Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
Applications
- Use in intercom/PA systems where indoor riser routing is required.
- Install in sound/audio systems that need consistent electrical performance in indoor installations.
- Specify for Fire Alarm applications (For color Red only)(Dual Rated) in indoor riser environments.
Belden™ and all associated trademarks are the property of their respective owners.
Spezifikationen
| Attribute | Value |
|---|---|
| Number of Conductors | 2 |
| Conductor size | 14 AWG |
| Stranding | 19x26 |
| Conductor Material | BC - Bare Copper |
| Insulation Material | PP - Polypropylene |
| Nom. thickness | 0.011 in (0.28 mm) |
| Nom. insulation diameter | 0.092 in (2.3 mm) |
| Color Code | Black, White |
| Jacket Material | PVC - Polyvinyl Chloride |
| Ripcord | Yes |
| Nom. jacket thickness | 0.017 in (0.43 mm) |
| Nom. diameter | 0.218 in (5.54 mm) |
| Overall cable diameter (nominal) | 0.218 in (5.54 mm) |
| Plenum number | 6100UH |
| Nom. conductor DCR | 2.53 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 22 pF/ft (72 pF/m) |
| Nom. inductance | 0.15 µH/ft (0.49 µH/m) |
| Max. current | 25 Amps per Conductor @ 30°C |
| Operating | -20°C to +75°C |
| UL temperature | 75°C |
| Bend radius (stationary min.) | 2.2 in (56 mm) |
| Bend radius (installation min.) | 2.2 in (56 mm) |
| Max Pull Tension | 95 lbs (43 kg) |
| Bulk cable weight | 33 lbs/1000ft |
| Environmental suitability | Indoor - Riser, Indoor |
| NEC / UL compliance | Article 725, Article 760, CL3R, FPLR |
| Flammability / reaction to fire | UL 1666 Riser, IEEE 1202 FT4, IEC 60332-1-2 |
| CPR Euroclass | Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Priced Per | FT |
Abbildungen dienen nur als Referenz. Spezifikationen können sich ohne Vorankündigung ändern — prüfen Sie vor dem Kauf die Eignung für Ihre Anwendung. Die Herstellerdokumentation ist maßgeblich.
Brauchen Sie einen Zuschnitt, Mengenpreise oder ein Datenblatt?
Unser Team erstellt Angebote für individuelle Längen und Großbestellungen, meist am selben Tag.