Belden 6100FL 002, FLRST FS 2C 14 AWG Red Audio Cable

SKU:Belden 6100FL 002
● Auf Lager
Beschreibung
Belden 6100FL 002 is a plenum-rated fire alarm cable (Plenum-FPLP) for fire alarm, monitor/detection, and circuits including audio, control, initiating, and notification in noisy environments. It is built with 2 14 AWG stranded bare copper conductors with Flamarrest® insulation, plus an overall Beldfoil® tape shield and drain wire for noise protection. A PVC - Polyvinyl Chloride outer jacket includes a ripcord, and the cable includes sequential footage marking every two feet. Designed for indoor use, it meets NFPA 262 (UL910), Article 760, and FPLP.
Key Features
- Plenum-rated fire alarm cable (Plenum-FPLP) for indoor installations.
- 2 14 AWG stranded bare copper conductors with Flamarrest® insulation.
- Overall Beldfoil® tape shield (foil side out) with 100% coverage and a drain wire for noise protection.
- PVC - Polyvinyl Chloride outer jacket with ripcord for easier installation.
- Sequential footage marking every two feet for measuring and pull tracking.
Technical Specs
Construction & Materials
| Number of Conductors | 2 |
|---|---|
| Conductor Size | 14 |
| Conductor Stranding | 19x26 |
| Conductor Material | BC - Bare Copper |
| Insulation Material | PVC - Polyvinyl Chloride |
| Nom. Thickness (Insulation) | 0.011 in (0.28 mm) |
| Nom. Insulation Diameter | 0.094 in (2.4 mm) |
| Color Code | Black, Red |
| Shield Type | Tape |
| Shield Material | Bi-Laminate (Alum+Poly) |
| Shield Coverage | 100% |
| Drainwire Type | 22 AWG (7x30) TC |
| Outer Jacket Material | PVC - Polyvinyl Chloride |
| Nom. Thickness (Jacket) | 0.015 in (0.38 mm) |
| Nom. Diameter | 0.218 in |
| Ripcord | Yes |
| Non-Plenum Number | 5100FL |
Electrical Characteristics
| Nom. Conductor DCR | 2.67 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 78.5 pF/ft (258 pF/m) |
| Nom. Capacitance Cond-to-other (conds + Shield) | 141.25 pF/ft (463.42 pF/m) |
| Nom. Outer Shield DCR | 10 Ohm/1000ft (33 Ohm/km) |
| Max. Current | 25 Amps per Conductor at 25ºC |
| UL Voltage Rating | 300 V |
Environmental & Mechanical Ratings
| UL Temperature | 75°C |
|---|---|
| Operating | 0°C To +75°C |
| Bend Radius (Stationary Min.) | 3.27 in (83.1 mm) |
| Bend Radius (Installation Min.) | 3.27 in |
| Max. Pull Tension | 104.1 lbs (47.22 kg) |
| Bulk Cable Weight | 38 lbs/1000ft |
| Environmental Suitability | Indoor |
| Flammability / Reaction to Fire | NFPA 262 (UL910), IEC 60332-1-2 |
Compliance & Certifications
| CPR Compliance | CPR Euroclass: Eca |
|---|---|
| NEC / UL Compliance | Article 760, FPLP |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
Applications
- Use in fire alarm installations where plenum-rated cable is required.
- Support monitor/detection circuits in indoor environments.
- Run audio, control, initiating, and notification circuits, including in noisy environments.
Belden™ and all associated trademarks are the property of their respective owners.
Spezifikationen
| Attribute | Value |
|---|---|
| Number of Conductors | 2 |
| Conductor size | 14 |
| Conductor stranding | 19x26 |
| Conductor Material | BC - Bare Copper |
| Insulation Material | PVC - Polyvinyl Chloride |
| Nom. thickness (insulation) | 0.011 in (0.28 mm) |
| Nom. insulation diameter | 0.094 in (2.4 mm) |
| Color Code | Black, Red |
| Shield Type | Tape |
| Shield Material | Bi-Laminate (Alum+Poly) |
| Shield Coverage | 100% |
| Drainwire type | 22 AWG (7x30) TC |
| Outer jacket material | PVC - Polyvinyl Chloride |
| Nom. thickness (jacket) | 0.015 in (0.38 mm) |
| Nom. diameter | 0.218 in |
| Ripcord | Yes |
| Non-Plenum number | 5100FL |
| Nom. conductor DCR | 2.67 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 78.5 pF/ft (258 pF/m) |
| Nom. capacitance cond-to-other (conds + Shield) | 141.25 pF/ft (463.42 pF/m) |
| Nom. outer shield DCR | 10 Ohm/1000ft (33 Ohm/km) |
| Max. current | 25 Amps per Conductor at 25ºC |
| UL Voltage Rating | 300 V |
| UL temperature | 75°C |
| Operating | 0°C To +75°C |
| Bend radius (stationary min.) | 3.27 in (83.1 mm) |
| Bend radius (installation min.) | 3.27 in |
| Max Pull Tension | 104.1 lbs (47.22 kg) |
| Bulk cable weight | 38 lbs/1000ft |
| Environmental suitability | Indoor |
| Flammability / reaction to fire | NFPA 262 (UL910), IEC 60332-1-2 |
| CPR compliance | CPR Euroclass: Eca |
| NEC / UL compliance | Article 760, FPLP |
| European directive compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Priced Per | FT |
Abbildungen dienen nur als Referenz. Spezifikationen können sich ohne Vorankündigung ändern — prüfen Sie vor dem Kauf die Eignung für Ihre Anwendung. Die Herstellerdokumentation ist maßgeblich.
Brauchen Sie einen Zuschnitt, Mengenpreise oder ein Datenblatt?
Unser Team erstellt Angebote für individuelle Längen und Großbestellungen, meist am selben Tag.