Contacto1-800-975-3686
Ramcorp Wire & Cable

Belden 29501F 010, Multi Conductor VFD Cable 3C 14 AWG Shielded 1000V TPE, Black Jacket

Belden 29501F 010, Multi Conductor VFD Cable 3C 14 AWG Shielded 1000V TPE, Black Jacket

SKU:Belden 29501F 010

$7.04/ FT

En stock

Descripción

Especificaciones

Belden 29501F 010, Multi Conductor VFD Cable 3C 14 AWG Shielded 1000V TPE, Black Jacket specifications
AttributeValue
Product typeVFD
Number of Conductors3
Conductor size14 AWG
Conductor stranding104x34
Conductor MaterialTC - Tinned Copper
Ground wire1 x 14 AWG, 104x34, TC - Tinned Copper
Conductor insulation materialXLPO - Crosslink Polyolefin
Conductor insulation thickness (nominal)0.046 in (1.2 mm)
Conductor insulation diameter (nominal)0.167 in (4.24 mm)
Conductor color codeICEA Chart M4
Ground wire insulation materialPVC - Polyvinyl Chloride
Ground wire insulation thickness (nominal)0.046 in (1.2 mm)
Ground wire insulation diameter (nominal)0.167 in (4.24 mm)
Ground wire colorGreen/Yellow Stripe
Tape shieldTri-Laminate (Alum+Poly+Alum), 100% coverage
Braid shieldTinned Copper (TC), 86% coverage
Outer jacket materialTPE - Thermoplastic Elastomer
Jacket ColorBlack
SeparatorPolyester Tape
RipcordYes
ShieldedShielded
Shield TypeBraid
ArmorNo
CompositeNo
Earth/ground wiresYes
Nom. thickness0.073 in (1.9 mm)
Nom. diameter0.587 in (14.9 mm)
Overall cable diameter (nominal)0.587 in (14.9 mm)
Bulk cable weight216 lbs/1000ft
Nom. conductor DCR2.468 Ohm/1000ft; 2.73 Ohm/1000ft (8.96 Ohm/km)
Nom. capacitance cond-to-cond40 pF/ft (130 pF/m)
Nom. capacitance cond-to-other (conds + Shield)72 pF/ft (240 pF/m)
Nom. characteristic impedence46 Ohm
Nom. inductance0.213 µH/ft (0.699 µH/m)
Nom. velocity of prop.55%
Max. current25 Amps per Conductor at 30ºC (per NEC)
Nom. outer shield DCR1.08 Ohm/1000ft (3.54 Ohm/km)
Voltage range1KV
UL temperature90°C Dry, 90°C Wet
Operating temperature-40°C To +90°C
Bend radius (stationary min.)7.0 in (180 mm)
Bend radius (installation min.)7.0 in (180 mm)
Max Pull Tension340 lbs (150 kg)
Flammability / reaction to fireUL 1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL complianceArticle 336, Article 310, TC-ER, XHHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) complianceCIC, TC
ICEA complianceS-95-658
European directive complianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC complianceChina RoHS II (GB/T 26572-2011)
SustainabilityCA Prop 65
Priced PerFT

Las imágenes son solo de referencia. Las especificaciones pueden cambiar sin previo aviso — verifique la idoneidad para su aplicación antes de comprar. La documentación del fabricante prevalece.

¿Necesita un corte a medida, precio por volumen o una ficha técnica?

Nuestro equipo cotiza largos personalizados y pedidos por volumen, normalmente el mismo día.