Belden 5120UL 002 is a riser-rated fire alarm cable (FPLR) for commercial fire alarm and monitor/detection circuits, including audio, control, initiating, and notification runs. It is built with 2 14 AWG solid bare copper conductors, polypropylene insulation, and a PVC jacket. Installation and compliance details include a 300 V (FPLR) UL voltage rating, a 75°C UL temperature rating, and sequential footage marking every two feet.
Key Features
- Riser-rated fire alarm cable type: Riser-FPLR.
- 2 14 AWG solid bare copper conductors (BC - Bare Copper) for fire alarm and monitor/detection circuits.
- Polypropylene insulation (PP - Polypropylene) with insulation color code: Black, Red.
- PVC jacket (PVC - Polyvinyl Chloride) with ripcord: Yes.
- UL voltage rating: 300 V (FPLR) and UL temperature: 75°C.
- Sequential footage marking every two feet to support pull planning and installation layout.
Technical Specs
Construction & Materials
| Number of conductors | 2 |
|---|---|
| Conductor size | 14 AWG |
| Conductor stranding | Solid |
| Conductor material | BC - Bare Copper |
| Insulation material | PP - Polypropylene |
| Nom. insulation thickness | 0.010 in (0.25 mm) |
| Nom. insulation diameter | 0.0845 in (2.15 mm) |
| Insulation color code | Black, Red |
| Jacket material | PVC - Polyvinyl Chloride |
Electrical Characteristics
| Nom. conductor DCR | 2.43 Ohm/1000ft |
|---|---|
| Nom. capacitance cond-to-cond | 23 pF/ft (75 pF/m) |
| Nom. inductance | 0.15 μH/ft (0.49 μH/m) |
| Max. current | 25 Amps per Conductor @ 30°C |
Physical Dimensions & Handling
| Overall cable diameter (nominal) | 0.205 in (5.21 mm) |
|---|---|
| Bend radius (stationary min.) | 1.64 in (41.7 mm) |
| Bend radius (installation min.) | 1.64 in (41.7 mm) |
| Max. pull tension | 99 lbs (45 kg) |
| Bulk cable weight | 33 lbs/1000ft |
Environmental & Mechanical Ratings
| Operating temperature | -20°C to +75°C |
|---|---|
| Environmental suitability | Indoor - Riser, Indoor |
Compliance & Certifications
| NEC / UL compliance | Article 760, FPLR |
|---|---|
| Flammability / reaction to fire | UL 1666 Riser, IEEE 1202 FT4, IEC 60332-1-2 |
| CPR compliance | CPR Euroclass: Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
Applications
- Use in fire alarm and monitor/detection installations where circuits include audio, control, initiating, and notification runs.
Belden™ and all associated trademarks are the property of their respective owners.
Especificaciones
| Attribute | Value |
|---|---|
| Number of Conductors | 2 |
| Conductor size | 14 AWG |
| Conductor stranding | Solid |
| Conductor Material | BC - Bare Copper |
| Insulation Material | PP - Polypropylene |
| Nom. insulation thickness | 0.010 in (0.25 mm) |
| Nom. insulation diameter | 0.0845 in (2.15 mm) |
| Insulation color code | Black, Red |
| Jacket Material | PVC - Polyvinyl Chloride |
| Nom. conductor DCR | 2.43 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 23 pF/ft (75 pF/m) |
| Nom. inductance | 0.15 µH/ft (0.49 µH/m) |
| Max. current | 25 Amps per Conductor @ 30°C |
| Overall cable diameter (nominal) | 0.205 in (5.21 mm) |
| Bend radius (stationary min.) | 1.64 in (41.7 mm) |
| Bend radius (installation min.) | 1.64 in (41.7 mm) |
| Max Pull Tension | 99 lbs (45 kg) |
| Bulk cable weight | 33 lbs/1000ft |
| Operating temperature | -20°C to +75°C |
| Environmental suitability | Indoor - Riser, Indoor |
| NEC / UL compliance | Article 760, FPLR |
| Flammability / reaction to fire | UL 1666 Riser, IEEE 1202 FT4, IEC 60332-1-2 |
| CPR compliance | CPR Euroclass: Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Priced Per | FT |
Las imágenes son solo de referencia. Las especificaciones pueden cambiar sin previo aviso — verifique la idoneidad para su aplicación antes de comprar. La documentación del fabricante prevalece.
¿Necesita un corte a medida, precio por volumen o una ficha técnica?
Nuestro equipo cotiza largos personalizados y pedidos por volumen, normalmente el mismo día.