Belden 1000A 1 Pair 16 AWG schermato Tipo JX

Descrizione
Belden 1000A 010 è una cavo termocoppia Tipo JX con 1 coppia di solido conduttori 16AWG (Ferro+Costantino). Presenta PVC isolamento, un schermaturaBeldfoil® complessivo e un PVC guainanero. Le marcature includono PLTC-ER, ITC-ER, CMG, AWM 2464 e SUN RES.
Applicazioni
- Utilizzare per il cablaggio del segnale termocoppia di tipo JX dove sono necessari conduttori Ferro+Constantan.
- Installa dove sono specificate le PLTC-ER, ITC-ER, CMG o AWM 2464.
- Specificare per ambienti in cui è richiesta la marcatura SUN RES.
cavo Stampa
PLTC-ER ITC-ER CMG AWM 2464 SUN RESSpecifiche
| Attribute | Value |
|---|---|
| Thermocouple type | Iron/Constantan Type JX |
| Elements | pair(s) |
| Number of elements | 1 |
| Insulation Material | PVC - Polyvinyl Chloride |
| Nom. thickness | 0.021 in (0.53 mm) |
| Nom. insulation diameter | 0.093 in (2.4 mm) |
| Shield Material | Bi-Laminate (Alum+Poly) |
| Drainwire type | 18 AWG (16x30) TC |
| Outer jacket material | PVC - Polyvinyl Chloride |
| Nom. jacket thickness | 0.037 in (0.94 mm) |
| Nom. diameter | 0.264 in (6.71 mm) |
| Overall cable diameter (nominal) | 0.264 in (6.71 mm) |
| Nom. outer shield DCR | 5.93 Ohm/1000ft (19.5 Ohm/km) |
| Nom. conductor DCR | 24 Ohm/1000ft (79 Ohm/km); 121 Ohm/1000ft (397 Ohm/km) |
| Electricals table notes | Conductor DCR (Nom): 24 Ohm/1000ft (Iron), 121 Ohm/1000ft (Constantan) |
| Nom. capacitance cond-to-cond | 25 pF/ft (82 pF/m) |
| Nom. capacitance (Cond-to-Shield) | 51 pF/ft (170 pF/m) |
| Nom. inductance cond-grnd | .18 µH/ft |
| Max. current | 18 Amps per Conductor @ 30°C |
| UL Voltage Rating | 300 V (PLTC, CMG, AWM 2464), 150 V (ITC) |
| UL temperature | 105°C |
| Operating | -30°C to +105°C |
| Stationary min. bend radius | 3.1 in (79 mm) |
| Installation min. bend radius | 3.1 in (79 mm) |
| Max Pull Tension | 83 lbs (38 kg) |
| Bulk cable weight | 38 lbs/1000ft (57 kg/km) |
| Environmental suitability | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance |
| Flammability / reaction to fire | UL 1685 FT4 Loading, FT4, IEEE 1202 FT4 |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | ISA MC 96.1-1982 Type JX |
| Item Type | Belden Thermocouple Wire |
| Other Part Numbers | 1000A 010, 1000A 010100, 1000A 010250, 1000A 010500, 1000A 0101000 |
| Priced Per | FT |