Belden 29522C 010, Cabo VFD, 3C-12 AWG BC + 3G-16 AWG BC, XLPE, Blindado, Jaqueta Preta

SKU:Belden 29522C 010
$364.80
● Em estoque
Descrição
Belden 29522C 010, Cabo VFD, 3C-12 AWG BC + 3G-16 AWG BC, XLPE, Blindado, Jaqueta Preta
Belden Básico 600V VFD
3-12 condutores de cobre nu encordoados (7x20) + fios de terra segmentados de cobre nu simétricos de 3-16 AWG
Isolamento XLPE em condutores, código de cores M4
Fitas de cobre duplas em geral com blindagem aplicado helicoidalmente
Revestimento de PVC total, ripcord
600/1000 V TC-ER, 90ºC Molhado/Seco
Especificações
| Attribute | Value |
|---|---|
| Number of Conductors | 3 |
| Conductor size | 12 AWG |
| Conductor stranding | 7x20 |
| Conductor Material | BC - Bare Copper |
| Segmented ground wire | 3 x 16 AWG |
| Ground stranding | 7x24 |
| Ground material | BC - Bare Copper |
| Ground notes | 3 Ground Segments totaling 12 AWG |
| Insulation Material | XLPE - Cross-Linked Polyethylene (Thermoset) |
| Nom. thickness | 0.030 in (0.76 mm) |
| Nom. insulation diameter | 0.153 in (3.89 mm) |
| Color Code | ICEA Chart M4 |
| Ground wire insulation | No Insulation |
| Shield Type | Helical Tape |
| Shield Material | Bare Copper (BC) |
| Coverage | 100% |
| Outer jacket material | PVC - Polyvinyl Chloride |
| Jacket Color | Black |
| Nom. jacket thickness | 0.060 in (1.5 mm) |
| Nom. conductor DCR | 1.423 Ohm/1000ft (4.669 Ohm/km) |
| Nom. capacitance cond-to-cond | 29 pF/ft (95 pF/m) |
| Nom. capacitance cond-to-other (conds + Shield) | 56 pF/ft (180 pF/m) |
| Nom. characteristic impedence | 50 Ohm |
| Nom. velocity of prop. | 55% |
| Max. current | 30 Amps per Conductor at 30ºC |
| Nom. outer shield DCR | 0.97 Ohm/1000ft (3.2 Ohm/km) |
| Nom. diameter | 0.460 in (11.7 mm) |
| Stationary min. bend radius | 5.5 in (140 mm) |
| Installation min. bend radius | 5.5 in (140 mm) |
| Max Pull Tension | 283 lbs (128 kg) |
| Bulk cable weight | 191 lbs/1000ft (284 kg/km) |
| Sustainability | CA Prop 65 |
| Flammability / reaction to fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL compliance | Article 336, TC-ER |
| ICEA compliance | S-95-658 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | P-07-KA070003-MSHA |
| Other Part Numbers | 29522C 010, 29522C 010100, 29522C 010250, 29522C 010500, 29522C 0101000 |
| Priced Per | FT |
Documentos
As imagens são apenas para referência. As especificações podem mudar sem aviso — verifique a adequação à sua aplicação antes de comprar. A documentação do fabricante prevalece.
Precisa de um corte sob medida, preço por volume ou uma ficha técnica?
Nossa equipe cotiza comprimentos personalizados e pedidos por volume, normalmente no mesmo dia.