Belden 1066A 010, Power Limited Tray Cable 12PR 18 AWG 600V PVC, Black Jacket

SKU:Belden 1066A
● In stock
Description
Belden 1066A 010 is a UL instrumentation, power limited tray cable designed for signal and control wiring in industrial environments. It is built with 12 pair 18 AWG (7x26) BC - Bare Copper stranded conductors, PVC-NYL insulation, and a PVC outer jacket in black. For noise reduction, it includes an overall Beldfoil® shield with 100% coverage. Key ratings and markings include UL voltage rating: 600 V (TC-ER), 150 V (NPLF) and SUN RES DIR BUR.
Belden 1066A 010 Key Features
- 12 pair 18 AWG (7x26) stranded conductors using BC - Bare Copper for instrumentation and control wiring builds.
- PVC-NYL insulation with E1 color code to support easier identification during installation and maintenance.
- Overall Beldfoil® shield with 100% coverage to help reduce noise in instrumentation and low voltage digital control circuits.
- UL voltage rating: 600 V (TC-ER), 150 V (NPLF) for tray cable and power-limited circuit requirements.
- Environmental suitability: indoor, outdoor, sunlight resistance, burial with manufacturer environmental marking: SUN RES DIR BUR.
Belden 1066A 010 Applications
- Supports industrial control wiring where reliable signal and control connections are needed.
- Installs in raceways, cable trays, and ducts to help organize and route control and instrumentation runs.
- Performs in digital control and low voltage digital control (24v, …) circuits where noise reduction is important.
- Connects instrumentation signals such as Instruments (4-20ma, 0-10v, ...) in control and monitoring systems.
- Fits encoder connections and other control circuits that require shielded signal wiring.
- Integrates into distributed control system (DCS) and programmable logic controller (PLC) wiring for plant automation.
- Commonly used for field device connections including Solenoids, Valves, Actuators, and Positioners.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Cable type | UL instrumentation, power limited tray Cable |
| Conductor count | 12 Pair |
| Conductor size | 18 AWG |
| Stranding | 7x26 |
| Conductor Material | BC - Bare Copper |
| Conductor Type | Stranded Conductor |
| Insulation Material | PVC/Nylon - Polyvinyl Chloride + Nylon |
| Insulation material (callout) | VN-Vinyl Nylon |
| Nom. insulation thickness | 0.022 in (0.56 mm) |
| Nom. insulation diameter | 0.088 in (2.2 mm) |
| Color Code | Black and White and Numbered |
| Shield | Yes - This has a Shield |
| Shield Type | Tape |
| Shield Material | Bi-Laminate (Alum+Poly) |
| Shield type (overall) | Overall Aluminum Mylar Foil Shield |
| Drainwire type | 18 AWG (7x26) TC |
| Outer jacket material | PVC - Polyvinyl Chloride |
| Jacket Color | Black |
| Nom. jacket thickness | 0.064 in (1.6 mm) |
| Ripcord | Yes |
| Armor | No |
| Thermocouple | No |
| Nom. outer shield DCR | 4.22 Ohm/1000ft (13.8 Ohm/km) |
| Nom. conductor DCR | 6.6 Ohm/1000ft |
| Max. current | 7 Amps per Conductor at 25ºC |
| Overall cable diameter (nominal) | 0.717 in |
| Stationary min. bend radius | 8.604 in (218.5 mm) |
| Installation min. bend radius | 8.604 in |
| Max Pull Tension | 560 lbs (250 kg) |
| Bulk cable weight | 272 lbs/1000ft |
| UL temperature | 90°C Dry, 90°C Wet |
| Operating | -20°C to +90°C |
| Flammability / reaction to fire | UL1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL compliance | Article 336, Article 760 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Priced Per | FT |
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.