Belden 1078A 010, Power Limited Tray Cable 12PR 20 AWG 300V PVC, Black Jacket

SKU:Belden 1078A
● In stock
Description
Belden 1078A 010 is a UL instrumentation power limited tray cable for industrial control and signal applications, including DCS and PLC systems, control circuits, and instrumentation loops (4-20ma, 0-10v, ...). It features 12 twisted pairs of 20 AWG (7x28) BC - Bare Copper conductors plus 1 22 AWG (7x30) BC - Bare Copper comm wire, insulated with PVC - Polyvinyl Chloride. For noise protection, the pairs are individually shielded, and the cable includes an overall Tape, Bi-Laminate (Alum+Poly), 100% shield under a black PVC - Polyvinyl Chloride outer jacket with a ripcord. UL Voltage Rating is 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC), with Indoor/Outdoor and Sunlight Resistance suitability.
Belden 1078A 010 Key Features
- UL instrumentation power limited tray cable for industrial control and signal applications.
- 12 twisted pairs of 20 AWG (7x28) BC - Bare Copper conductors plus 1 22 AWG (7x30) BC - Bare Copper comm wire.
- PVC - Polyvinyl Chloride insulation on pairs and comm wire.
- Individual and overall shields, including Tape, Bi-Laminate (Alum+Poly), 100% coverage.
- Black PVC - Polyvinyl Chloride outer jacket with ripcord; Armor: No.
- UL Voltage Rating: 300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC).
- Environmental suitability: Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance.
- UL / cable type markings: UL Instrumentation; PLTC ITC CMG AWM 2464 SUN RES.
Belden 1078A 010 Applications
- Use in industrial control where a UL instrumentation power limited tray cable is specified.
- Install in raceways, cable trays, and ducts.
- Support digital control and low voltage digital control (24v, …) signal distribution.
- Apply in instrumentation loops (4-20ma, 0-10v, ...) for control and monitoring systems.
- Connect field devices to control equipment in control circuits.
- Deploy in distributed control system (DCS) architectures for plant-wide control and I/O connectivity.
- Integrate with programmable logic controller (PLC) systems for automation and machine/process control.
- Install for encoders where shielded signal wiring is required.
- Connect solenoids within industrial control systems.
- Use for valves in automated control circuits.
- Use for actuators in control and positioning systems.
- Use for positioners in instrumentation and control loops.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Pairs | 12 |
| Pair Conductor Size | 20 AWG |
| Pair Stranding | 7x28 |
| Pair Conductor Material | BC - Bare Copper |
| Comm Wire(s) | 1 |
| Comm Wire size | 22 AWG |
| Comm Wire stranding | 7x30 |
| Comm Wire material | BC - Bare Copper |
| Insulation thickness (pairs) | 0.018 in (0.46 mm) |
| Pair color code | Black, White and Numbered |
| Insulation thickness (comm wire) | 0.019 in (0.48 mm) |
| Comm Wire color | Orange |
| Inner shield (pair(s)) | Tape, Bi-Laminate (Alum+Poly), 100% |
| Inner shield drainwire (pairs) | 22 AWG (7x30) TC |
| Outer shield | Tape, Bi-Laminate (Alum+Poly), 100% |
| Outer shield drainwire | 20 AWG (7x28) TC |
| Jacket Thickness | 0.063 in (1.6 mm) |
| Overall cable diameter (nominal) | 0.637 in (16.2 mm) |
| Bulk cable weight | 243 lbs/1000ft |
| Nom. Conductor DCR (pairs) | 9.5 Ohm/1000ft (31 Ohm/km) |
| Nom. capacitance cond-to-cond (pair(s)) | 30 pF/ft (98 pF/m) |
| Nom. capacitance cond-to-shield (pairs) | 55 pF/ft (180 pF/m) |
| Nom. inductance (pair(s)) | 0.19 µH/ft (0.62 µH/m) |
| Max. Current (pair(s)) | 3 Amps per Conductor @ 25°C |
| Nom. conductor DCR (comm wire) | 14.7 Ohm/1000ft (48.2 Ohm/km) |
| Nom. outer shield DCR | 6.5 Ohm/1000ft (21 Ohm/km) |
| UL temperature | 105°C |
| Operating temperature | -30°C to +105°C |
| Bend radius (stationary min.) | 6.4 in (160 mm) |
| Bend radius (installation min.) | 6.4 in (160 mm) |
| Max Pull Tension | 468 lbs (212 kg) |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| Flammability / reaction to fire | UL1685 (FT4 Loading), FT4, T-29-520, 1202 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Priced Per | FT |
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.