Description
Belden 29530 010 is a 100% ground flexible VFD cable engineered for Variable Frequency Drives (VFD) and AC motor and drive systems, including Class 1 Division 2 hazardous locations. It features 3 finely stranded 2/0 AWG TC - Tinned Copper conductors with XLPE - Cross-Linked Polyethylene (Thermoset) insulation and ICEA Chart M4 color coding. For noise control and durability, it includes an overall dual copper tape helically applied shield with 100% coverage and a black PVC - Polyvinyl Chloride outer jacket with a ripcord. UL Voltage Rating is 1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC).
Belden 29530 010 Key Features
- 3 finely stranded 2/0 AWG TC - Tinned Copper conductors with Conductor Stranding: 7x19x20.
- XLPE - Cross-Linked Polyethylene (Thermoset) insulation with ICEA Chart M4 color coding.
- (3) symmetrical segmented BC - Bare Copper ground wires; Ground size: 4 AWG; Ground Stranding: 7x19x25; Ground Wire: No Insulation.
- Overall dual copper tape helically applied shield with 100% coverage; Shield Material: Bare Copper (BC).
- Black PVC - Polyvinyl Chloride jacket with Ripcord: Yes.
- UL Voltage Rating: 1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC).
- Environmental suitability: Indoor, Outdoor, Sunlight Resistance, Burial.
Belden 29530 010 Applications
- Use in Variable Frequency Drives (VFD) installations where a VFD cable is specified.
- Support AC motor and drive systems requiring a flexible power and control connection.
- Specify for Class 1 Division 2 hazardous locations when the installation calls for this cable type.
- Use recommended cable gland Belden BTC150A1501RA.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Notes (conductors) | Finely Stranded Tinned Copper optomized for VFD use |
| Earth/ground wires | Yes |
| Number of ground wires | 3 Wire |
| Segmented ground wire | 3 |
| Notes (grounds) | Segmented grounds (3 totaling 2/0 AWG) |
| Insulation thickness (nom.) | 0.057 in (1.4 mm) |
| Insulation diameter (nom.) | 0.552 in (14.0 mm) |
| Shield | Shielded |
| Shield Type | Copper tape |
| Outer shield type | Helical tape |
| Notes (shield) | 2 mil copper tape for crack resistance and high frequency noise conduction |
| Armor | No |
| Composite | No |
| Jacket thickness (nom.) | 0.083 in (2.1 mm) |
| Nom. diameter | 1.368 in (34.75 mm) |
| Overall cable diameter (nominal) | 1.368 in (34.75 mm) |
| Bulk cable weight | 2016 lbs/1000ft (3000 kg/km) |
| Voltage range | 1KV |
| Nom. Conductor DCR (Conductor(s)) | 0.075 Ohm/1000ft (0.25 Ohm/km) |
| Nom. capacitance cond-to-cond | 30 pF/ft (98 pF/m) |
| Nom. capacitance cond-to-other (conds + Shield) | 56 pF/ft (180 pF/m) |
| Nom. characteristic impedence | 36 Ohm |
| Nom. inductance cond-grnd | 0.067 µH/ft |
| Nom. velocity of prop. | 55% |
| Max. current | 195 Amps per Conductor at 30ºC |
| Nom. conductor DCR (segmented ground wire) | 0.08 Ohm/1000ft (0.26 Ohm/km) |
| Nom. outer shield DCR | 0.06 Ohm/1000ft (0.20 Ohm/km) |
| UL temperature | 90°C Dry, 90°C Wet |
| Operating | -40°C To +90°C |
| Stationary min. bend radius | 16.4 in (417 mm) |
| Installation min. bend radius | 16.4 in (417 mm) |
| Max Pull Tension | 6607 lbs (2997 kg) |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, IEEE 1202 FT4 |
| NEC / UL compliance | Article 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable |
| CEC / C(UL) compliance | TC |
| ICEA compliance | S-95-658 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | P-07-KA070003-MSHA |
| Sustainability | CA Prop 65 |
| Other Part Numbers | 29530 010, 29530 010100, 29530 010250, 29530 010500, 29530 0101000, UPC 612825138068 |
| Priced Per | FT |