Belden 3085A 560, Multi Conductor DeviceBus 2 22 AWG 2 24 AWG Shield CPE

SKU:Belden 3085A 560
● In stock
Description
Belden 3085A 560 is a DeviceBus® for ODVA DeviceNet™ Cable designed for harsh environment, device-level communication in industrial automation networks. It combines a 22 AWG power pair and a 24 AWG data pair with stranded tinned copper conductors, using PVC insulation on the power pair and PE - Polyethylene (Foam) insulation on the data pair. For noise immunity, each pair is shielded with 100% Beldfoil® tape shielding plus an overall tinned copper braid shield with 65% coverage. The rugged CPE outer jacket supports indoor/outdoor use with sunlight resistance and carries CMG, CL2 ratings with a 300 V (CMG, CL2) UL Voltage Rating.
Belden 3085A 560 Key Features
- DeviceBus® for ODVA DeviceNet™ Cable designed for harsh environment, device-level communication in industrial automation networks.
- 22 AWG power pair and 24 AWG data pair with stranded tinned copper conductors.
- PVC insulation on the power pair and PE - Polyethylene (Foam) insulation on the data pair.
- Shielding includes 100% Beldfoil® tape shielding on each pair plus an overall tinned copper braid shield with 65% coverage.
- CPE - Chlorinated Polyethylene jacket for indoor, outdoor, sunlight resistance.
- CMG, CL2 with UL Voltage Rating: 300 V (CMG, CL2).
Belden 3085A 560 Applications
- Use it in harsh environment installations where device-level communication is required.
- Support ODVA device-level communication in industrial automation networks with this cable.
- Deploy it with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Power pair(s) | 1 pair, 22 AWG, 19x34, TC - Tinned Copper |
| Data pair(s) | 1 pair, 24 AWG, 19x36, TC - Tinned Copper |
| Conductor Type | Stranded Conductor |
| Conductor Material | Tinned Copper |
| Power insulation | PVC - Polyvinyl Chloride, 0.021 in (0.53 mm) nominal thickness, 0.072 in (1.8 mm) nominal Insulation Diameter, Red & Black |
| Data insulation | PE - Polyethylene (Foam), 0.026 in (0.66 mm) nominal thickness, 0.077 in (2.0 mm) nominal Insulation Diameter, Blue & White |
| Insulation Material | Comb-different insulations for composites |
| Shielded | Yes |
| Inner shield (power pair(s)) | Tape, Bi-Laminate (Alum+Poly), 100% |
| Inner shield (data pair(s)) | Tape, Bi-Laminate (Alum+Poly), 100% |
| Outer shield | Braid, Tinned Copper (TC), 65% |
| Drainwire type | 22 AWG (19x34) TC |
| Shield Type | Braid over Foil Shield |
| Shield construction | Overall & individual shields w/drain |
| Jacket Material | CPE - Chlorinated Polyethylene |
| Nom. jacket thickness | 0.033 in (0.84 mm) |
| Overall cable diameter (nominal) | 0.280 in (7.11 mm) |
| Jacket OD +/- | 0.005 |
| Power pair(s) nominal Conductor DCR | 18.2 Ohm/1000ft |
| Power Pair(s) max. Conductor DCR | 17.5 Ohm/1000ft |
| Power pair(s) nominal inner Shield DCR | 7.95 Ohm/1000ft (26.1 Ohm/km) |
| Power pair(s) max. current | 6 Amps per Conductor at 30ºC |
| Data pair(s) nominal Conductor DCR | 28.8 Ohm/1000ft (94.5 Ohm/km) |
| Data Pair(s) max. Conductor DCR | 28 Ohm/100m |
| Data pair(s) nominal inner Shield DCR | 7.45 Ohm/1000ft (24.4 Ohm/km) |
| Data pair(s) nominal capacitance Cond-to-Cond | 12.0 pF/ft (39.4 pF/m) |
| Data pair(s) nominal characteristic impedence | 120 Ohm |
| Data pair(s) nominal delay | 1.36 ns/ft |
| Data pair(s) nominal velocity of prop. | 75% |
| Data pair(s) max. current | 6 Amps per Conductor at 30ºC |
| Nom. outer shield DCR | 5 Ohm/1000ft (16 Ohm/km) |
| UL temperature | 75°C |
| Operating temperature | -20°C to +75°C |
| Bend radius (stationary min.) | 2.8 in (71 mm) |
| Bend radius (installation min.) | 2.8 in (71 mm) |
| Max Pull Tension | 70.06 lbs (31.78 kg) |
| Bulk cable weight | 46 lbs/1000ft |
| Flammability / reaction to fire | UL 1685 FT4 Loading, IEEE 1202 FT4, IEC 60332-1-2 |
| CPR compliance | CPR Euroclass: Eca |
| NEC / UL compliance | Article 725, Article 800, CL2, CMG |
| CEC / C(UL) compliance | CMG |
| NEC rating | UL Listed Art 725 CLASS 2 |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | ODVA Class 2 Thin |
| Item Type | Belden Multi Conductor Cable |
| Other Part Numbers | 3085A 560, 3085A 560100, 3085A 560250, 3085A 560500, 3085A 5601000 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.