Belden 6122FL 002, Fire Alarm Cable FPLP 4C 14 AWG Shielded Plenum, Red Jacket

Description
Belden 6122FL 002 is a plenum-rated Fire Alarm Cable (Plenum-FPLP) designed for Fire Alarm, monitor/detection, and circuit applications, including audio, control, initiating, and notification in noisy environments. It is built with 4 solid 14 AWG BC - Bare Copper conductors with PVC - Polyvinyl Chloride insulation and an overall Beldfoil® shield with a 22 AWG (Solid) TC drainwire. The cable features a red PVC - Polyvinyl Chloride jacket with ripcord and is rated 300 V with a 75°C UL Temperature Rating. It is compliant with NFPA 262 (UL910) for indoor plenum pathways.
Belden 6122FL 002 Key Features
- Plenum-rated Fire Alarm Cable (Plenum-FPLP) for Fire Alarm, monitor/detection, and circuit applications, including audio, control, initiating, and notification in noisy environments.
- 4 solid 14 AWG BC - Bare Copper conductors with PVC - Polyvinyl Chloride insulation.
- Overall Beldfoil® shield with a 22 AWG (Solid) TC drainwire for noise protection.
- Red PVC - Polyvinyl Chloride jacket with ripcord for easier stripping and installation.
- Rated 300 V with a 75°C UL Temperature Rating.
- NFPA 262 (UL910) compliant for indoor plenum pathways.
Belden 6122FL 002 Applications
- Supports Fire Alarm system wiring where dependable signal transmission is needed for monitoring and detection functions.
- Meets circuit needs for audio, control, initiating, and notification functions within Fire Alarm installations.
- Works in noisy environment installations where shielding helps reduce the impact of electrical noise.
- Fits indoor plenum pathways where NFPA 262 (UL910) compliance is required.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Insulation thickness (nom.) | 0.012 in (0.30 mm) |
| Insulation diameter (nom.) | 0.089 in (2.3 mm) |
| Color Code | Black, Red, Brown, Blue |
| Shield Type | Tape |
| Shield Material | Bi-Laminate (Alum+Poly) |
| Shield Coverage | 100% |
| Jacket thickness (nom.) | 0.015 in (0.38 mm) |
| Overall cable diameter (nominal) | 0.245 in |
| Nom. diameter | 0.245 in |
| Bulk cable weight | 73 lbs/1000ft |
| Nom. conductor DCR | 2.43 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 46 pF/ft (150 pF/m) |
| Nom. capacitance cond-to-other (conds + Shield) | 82.8 pF/ft (272 pF/m) |
| Max. current | 6.4 Amps per Conductor at 25ºC |
| Nom. outer shield DCR | 10.6 Ohm/1000ft (34.8 Ohm/km) |
| Operating | 0°C to +75°C |
| Bend radius (stationary min.) | 3.67 in (93.2 mm) |
| Bend radius (installation min.) | 3.67 in |
| Max Pull Tension | 207 lbs (93.9 kg) |
| Environmental suitability | Indoor |
| NEC / UL compliance | Article 760, FPLP |
| European directive compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | California State Fire Marshall |
| Non-Plenum number | 5122FL |
| Item Type | Belden Multi Conductor Cable |
| Other Part Numbers | 6122FL 0021000, UPC 612825173793 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.