Belden 82641 877 is a Computer EIA RS-232 Cable with a 1-pair, 24 AWG stranded (7x32) design, FEP insulation, and a Flamarrest® jacket. It features an overall Beldfoil® shield (100% coverage) with a 24 AWG (7x32) TC drain wire to help reduce EMI/RFI. The cable is rated CMP with a UL voltage rating of 300 V (CMP) and is intended for indoor - plenum, indoor environments.
Belden 82641 877 Key Features
- 1-pair construction with 24 AWG stranded (7x32) conductors.
- TC - tinned copper conductor material.
- FEP - fluorinated ethylene propylene insulation with black & red color code.
- Overall Beldfoil® tape shield with bi-laminate (Alum+Poly) material and 100% coverage.
- 24 AWG (7x32) TC drain wire included with the overall shield.
- Flamarrest® jacket with PVC - polyvinyl chloride material and natural jacket color.
- CMP rating with UL voltage rating: 300 V (CMP).
- Environmental suitability listed as indoor - plenum, indoor.
Belden 82641 877 Applications
- Commonly used for RS-232 applications where computer communications are required.
- Supports indoor plenum applications in spaces where plenum-rated cable is specified.
- Suitable for panel wiring where low voltage signal connections are needed.
- Can be used for line level audio signal runs.
- Used for low voltage analog signals (4-20ma, 0-10v, ...).
- Used for low voltage digital control (24v, …).
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Insulation thickness (nom.) | 0.006 in (0.15 mm) |
| Insulation diameter (nom.) | 0.036 in (0.91 mm) |
| Jacket thickness (nom.) | 0.015 in (0.38 mm) |
| Cable diameter (nom.) | 0.108 in (2.74 mm) |
| Bulk cable weight | 8 lbs/1000ft |
| Conductor DCR (nom.) | 24.1 Ohm/1000ft |
| Shield DCR (nom.) | Nom outer shield DCR: 28.8 Ohm/1000ft (94.5 Ohm/km) |
| Capacitance, Cond-to-Cond (nom.) | 31 pF/ft (100 pF/m) |
| Capacitance, Cond-to-other (nom.) | 59 pF/ft (190 pF/m) |
| Inductance (nom.) | 0.17 µH/ft (0.56 µH/m) |
| Max. current | 2.2 Amps per conductor at 25ºC |
| UL temperature | 60°C |
| Operating temperature | 0°C to +60°C |
| Bend radius (stationary min.) | 1.08 in (27.4 mm) |
| Bend radius (installation min.) | 1.08 in (27.4 mm) |
| Max Pull Tension | 16 lbs (7.3 kg) |
| Flammability / reaction to fire | NFPA 262, UL 910 (Plenum) |
| NEC / UL compliance | Article 800, CMP |
| CEC / C(UL) compliance | CMP |
| CPR compliance | CPR Euroclass: Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Sustainability | CA Prop 65 |
| Plenum number | 88641 |
| Non-Plenum number | 8641 |
| Item Type | Belden Multi-Pair Cable |
| Other Part Numbers | 82641 877100; 82641 877250; 82641 877500; 82641 8771000 UPC 612825197508 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.