Belden 8469 060, Multi Conductor Cable 9C 18 AWG PVC Jacket, Chrome Jacket

SKU:Belden 8469 060
● In stock
Description
Belden 8469 060 is a 9-conductor 18 AWG multi-conductor cable with 19x30 TC - Tinned Copper stranded conductors, PVC insulation, and a PVC outer jacket. It features a Chrome jacket and is rated 300 V (CMG), 300 V (UL AWM 2598), with a max. current of 9.8 Amps per Conductor at 30ºC. This cable is intended for indoor electronic and control wiring where dependable multi-conductor performance is needed.
Belden 8469 060 Key Features
- 9 conductors in a single multi-conductor construction for consolidated wiring runs.
- 18 AWG conductors with 19x30 TC - Tinned Copper stranding for flexibility.
- PVC - Polyvinyl Chloride insulation and a PVC - Polyvinyl Chloride outer jacket.
- 300 V (CMG), 300 V (UL AWM 2598) voltage rating for applicable installations.
- Max. current of 9.8 Amps per Conductor at 30ºC for circuit design reference.
- Suitable for indoor environments.
- Jacket color: Chrome.
- Shield: No.
Belden 8469 060 Applications
- Suitable for low voltage analog signals (4-20ma, 0-10v, ...) in indoor electronic and control wiring.
- Designed for low voltage control (24v, …) where multi-conductor routing supports organized panel and control wiring.
- Applicable to line level audio connections in indoor installations.
- Supports voice communications wiring where an indoor-rated multi-conductor cable is required.
- Commonly used for panel wiring to help manage multiple circuits within control enclosures.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Conductor Material | TC - Tinned Copper |
| Color Code | Black, White, Red, Green, Brown, Blue, Orange, Yellow, Purple |
| Insulation thickness (nom.) | 0.018 in (0.46 mm) |
| Insulation diameter (nom.) | 0.080 in (2.0 mm) |
| Outer jacket thickness (nom.) | 0.037 in (0.94 mm) |
| Overall cable diameter (nom.) | 0.364 in (9.25 mm) |
| Bulk cable weight | 89 lbs/1000ft |
| Conductor DCR (nom.) | 7.13 Ohm/1000ft |
| Capacitance, Cond-to-Cond (nom.) | 26 pF/ft (85 pF/m) |
| UL temperature | 60°C |
| Operating temperature | -20°C to +60°C |
| Bend radius (stationary min.) | 3.6 in (91 mm) |
| Bend radius (installation min.) | 3.6 in (91 mm) |
| Max Pull Tension | 222 lbs (101 kg) |
| NEC / UL compliance | Article 800, CMG |
| CEC / C(UL) compliance | CMG |
| AWM compliance | AWM 2598 |
| Flammability / reaction to fire | UL 1685 FT4 Loading, FT4, IEC 60332-1-2 |
| CPR compliance | CPR Euroclass: Eca |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Multi Conductor Cable |
| Other Part Numbers | 8469 060100, 8469 060250, 8469 060500, 8469 0601000, UPC 612825208488 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.