Belden 9331 060, Power Limited Tray Cable 6PR 22 AWG 300V PVC, Chrome Jacket

SKU:Belden 9331 060
● In stock
Description
Belden 9331 060 is an instrumentation PLTC tray cable for signal transmission in industrial control and monitoring systems. It features 6 pair 22 AWG (7x30) TC - Tinned Copper conductors with PVC - Polyvinyl Chloride insulation and ICEA Chart E2 color coding. Each pair is individually shielded with Tape (Bi-Laminate (Alum+Poly)) at 100% coverage and includes a 22 AWG (7x30) TC drainwire. The cable is rated 300 V (PLTC, CMG) and finished with a PVC - Polyvinyl Chloride outer jacket in Chrome, suitable for Indoor/Outdoor use with Sunlight Resistance.
Belden 9331 060 Key Features
- 6 pair construction with 22 AWG (7x30) TC - Tinned Copper conductors for instrumentation and control wiring.
- PVC - Polyvinyl Chloride insulation with ICEA Chart E2 color coding for consistent pair identification.
- Individually shielded pairs using Tape (Bi-Laminate (Alum+Poly)) with 100% coverage, plus a 22 AWG (7x30) TC drainwire on each pair.
- 300 V (PLTC, CMG) UL voltage rating for PLTC and CMG installations.
- PVC - Polyvinyl Chloride outer jacket in Chrome with ripcord for handling and installation support.
- Environmental suitability listed as Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance.
Belden 9331 060 Applications
- Use it for instrumentation signal wiring in industrial control and monitoring systems.
- Connect sensors, valves, and positioners where reliable signal transmission is required.
- Specify it for 4-20mA and 0-10V signal applications.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Number of elements | 6 |
| Element type | pair(s) |
| Insulation thickness (nom.) | 0.017 in (0.43 mm) |
| Insulation diameter (nom.) | 0.062 in (1.6 mm) |
| Separator | Cotton Serve |
| Jacket thickness (nom.) | 0.053 in (1.3 mm) |
| Overall cable diameter (nom.) | 0.457 in (11.6 mm) |
| Armor | No |
| Bulk cable weight | 101 lbs/1000ft |
| Conductor DCR (nom.) | 18.2 Ohm/1000ft |
| Inner shield DCR (nom.) | 13.37 Ohm/1000ft (43.86 Ohm/km) |
| Capacitance, Cond-to-Cond (nom.) | 26 pF/ft (85 pF/m) |
| Capacitance Cond-to-Shield (nom.) | 45 pF/ft (150 pF/m) |
| Inductance (nom.) | 0.21 µH/ft (0.69 µH/m) |
| Max. current | 2.1 Amps per Conductor at 25ºC |
| UL temperature | 105°C |
| Operating temperature | -30°C to +105°C |
| Temperature table notes | AWM 80°C |
| Stationary min. bend radius | 4.6 in (120 mm) |
| Installation min. bend radius | 4.6 in (120 mm) |
| Max Pull Tension | 118 lbs (53.5 kg) |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, T-29-520, IEEE 1202 |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Other Part Numbers | 9331 060100; 9331 060250; 9331 060500 UPC 612825230731; 9331 0601000 UPC 612825230724 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.