Belden 9369 060, Power Limited Tray Cable 3PR 18 AWG 300V PVC, Chrome Jacket

SKU:Belden 9369 060
● In stock
Description
Belden 9369 060 is an instrumentation cable designed for power-limited tray installations, featuring 3 pair 18 AWG (19x30) TC - Tinned Copper conductors with PVC - Polyvinyl Chloride insulation and a PVC - Polyvinyl Chloride outer jacket. Each pair uses Tape, Bi-Laminate (Alum+Poly), 100% shielding and includes a 20 AWG (19x32) TC drainwire to help reduce noise in sensitive signal circuits. The cable is rated 300 V (PLTC, CMG) and 105°C, and it has a Chrome jacket specified for Indoor/Outdoor, Sunlight Resistance, and Burial.
Belden 9369 060 Key Features
- 3 pair construction with 18 AWG conductors for instrumentation and control wiring.
- 19x30 TC - Tinned Copper conductor stranding with PVC - Polyvinyl Chloride insulation.
- Each pair is shielded with Tape, Bi-Laminate (Alum+Poly), 100% and includes a 20 AWG (19x32) TC drainwire to help reduce noise in sensitive signal circuits.
- Rated 300 V (PLTC, CMG) and UL temperature 105°C.
- Chrome PVC - Polyvinyl Chloride outer jacket with environmental suitability listed as Indoor/Outdoor, Sunlight Resistance, and Burial.
Belden 9369 060 Applications
- Use in instrumentation wiring where a shielded, power-limited tray cable is needed to support signal integrity in sensitive circuits.
- Deploy with sensors in indoor or outdoor environments where Sunlight Resistance and Burial are specified.
- Install on valves and positioners where paired conductors and individual pair shielding help manage electrical noise.
- Support 4-20mA signal circuits where noise reduction is important for stable measurement and control signals.
- Apply in 0-10V signal circuits used for control and monitoring where shielded pairs help reduce interference.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Number of elements | 3 |
| Element type | Pair(s) |
| Color Code | ICEA Chart E2 |
| Separator | PP - Polypropylene Tape |
| Ripcord | Yes |
| Armor | No |
| Thermocouple | No |
| Insulation thickness (nom.) | 0.019 in (0.48 mm) |
| Insulation diameter (nom.) | 0.082 in (2.1 mm) |
| Overall cable diameter (nom.) | 0.456 in (11.6 mm) |
| Outer jacket thickness (nom.) | 0.053 in (1.3 mm) |
| Outer jacket diameter (nom.) | 0.456 in (11.6 mm) |
| Bulk cable weight | 105 lbs/1000ft |
| Nom. conductor DCR | 7.2 Ohm/1000ft |
| Nom. inner shield DCR | 8.18 Ohm/1000ft (26.8 Ohm/km) |
| Nom. capacitance cond-to-cond | 57 pF/ft (190 pF/m) |
| Nom. capacitance (Cond-to-Shield) | 102 pF/ft (335 pF/m) |
| Nom. inductance | 0.18 µH/ft (0.59 µH/m) |
| Max. current | 3.5 Amps per Conductor at 25ºC |
| Bend radius (stationary min.) | 4.5 in (110 mm) |
| Bend radius (installation min.) | 4.5 in (110 mm) |
| Max Pull Tension | 163 lbs (73.9 kg) |
| Operating temperature | -30°C to +105°C |
| Temperature table notes | AWM 80°C |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, T-29-520, IEEE 1202 |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Other Part Numbers | 9369 060100; 9369 060250; 9369 060500 UPC 612825239659; 9369 0601000 UPC 612825239635; 9369 0602500 UPC 612825239642; 9369 0605000 UPC 612825239666 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.