Belden 9388 060, Power Limited Tray Cable 4PR 18 AWG 300V PVC, Chrome Jacket

SKU:Belden 9388 060
● In stock
Description
Belden 9388 060 is an instrumentation PLTC cable with 4 pair 18 AWG (19x30) TC - Tinned Copper conductors, PVC - Polyvinyl Chloride insulation, and a PVC - Polyvinyl Chloride outer jacket in Chrome. It features an individual foil shield over each pair (each pair) using Bi-Laminate (Alum+Poly) tape with 100% coverage, plus a 20 AWG (19x32) TC drainwire type. The UL Voltage Rating is 300 V (PLTC, CMG), and it is rated for Operating: -30°C to +105°C with UL temperature: 105°C. Environmental suitability includes Indoor/Outdoor, Sunlight Resistance, and Burial.
Belden 9388 060 Key Features
- 4 pair 18 AWG (19x30) stranded conductor construction using TC - Tinned Copper.
- PVC - Polyvinyl Chloride insulation with color code: ICEA Chart E2.
- Individual foil shield over each pair (each pair) with Bi-Laminate (Alum+Poly) tape and 100% coverage, plus a 20 AWG (19x32) TC drainwire type.
- PVC - Polyvinyl Chloride outer jacket in Chrome with separator: PP - Polypropylene Tape and ripcord: Yes.
- UL Voltage Rating: 300 V (PLTC, CMG) with Operating: -30°C to +105°C and UL temperature: 105°C.
- Environmental suitability: Indoor/Outdoor, Sunlight Resistance, Burial.
Belden 9388 060 Applications
- Use it for instrumentation circuits where reliable signal transmission is needed.
- Support sensors, valves, and positioners in industrial control and process applications.
- Choose it for 4-20mA and 0-10V circuits.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Number of elements | 4 |
| Conductor Type | Stranded Conductor |
| Insulation nominal thickness | 0.017 |
| Nom. insulation diameter | 0.078 in (2.0 mm) |
| Shield | Yes - this has a shield |
| Shield Type | Tape |
| Jacket nominal thickness | 0.053 in (1.3 mm) |
| Overall cable diameter (nominal) | 0.489 in (12.4 mm) |
| Bulk cable weight | 122 lbs/1000ft |
| Armor | No |
| Thermocouple | No |
| Nom. conductor DCR | 7.2 Ohm/1000ft |
| Nom. inner shield DCR | 8.18 Ohm/1000ft (26.8 Ohm/km) |
| Nom. capacitance cond-to-cond | 57 pF/ft (190 pF/m) |
| Nom. capacitance (Cond-to-Shield) | 85 pF/ft (280 pF/m) |
| Nom. inductance | 0.18 μH/ft (0.59 μH/m) |
| Max. current | 3.5 Amps per Conductor at 25ºC |
| Temperature table notes | AWM 80°C |
| Bend radius (stationary min.) | 4.6 in (120 mm) |
| Bend radius (installation min.) | 4.6 in (120 mm) |
| Max Pull Tension | 212 lbs (96.2 kg) |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, T-29-520, IEEE 1202 |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Other Part Numbers | 9388 060100; 9388 060250; 9388 060500 UPC 612825239802; 9388 0601000 UPC 612825239796; 9388 0605000 UPC 612825239819 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.