Belden 9407 060, Power Limited Tray Cable 1PR 22 AWG 300V PVC, Chrome Jacket

SKU:Belden 9407 060
● In stock
Description
Belden 9407 060 is an instrumentation Power Limited Tray Cable (PLTC) built with 1 pair 22 AWG (7x30) TC - Tinned Copper stranded conductors and a PVC - Polyvinyl Chloride insulation and jacket. It uses an unshielded design (No Shield) with a ripcord for easier jacket removal and a Chrome jacket for clear identification. Rated 300 V (PLTC, CMG) with a UL temperature of 105°C, it supports reliable signal and control wiring in demanding installations.
Belden 9407 060 Key Features
- Instrumentation Power Limited Tray Cable (PLTC) construction for signal and control wiring.
- 1 pair 22 AWG (7x30) TC - Tinned Copper stranded conductors.
- PVC - Polyvinyl Chloride insulation and PVC - Polyvinyl Chloride outer jacket.
- Unshielded design (No Shield) with no armor.
- Ripcord included for easier jacket removal.
- Chrome jacket color for clear identification.
- UL voltage rating: 300 V (PLTC, CMG).
- UL temperature: 105°C.
Belden 9407 060 Applications
- Use it for instrumentation wiring where dependable signal and control connections are needed.
- Connect sensors, valves, and positioners in control and monitoring setups.
- Apply it in 4-20mA and 0-10V signal applications.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Elements | Pair(s) |
| Number of elements | 1 |
| Conductor size | 22 AWG |
| Stranding | 7x30 |
| Conductor Material | TC - Tinned Copper |
| Conductor Type | Stranded conductor |
| Color Code | Black & Red |
| Insulation thickness (nom.) | 0.017 in (0.43 mm) |
| Insulation diameter (nom.) | 0.062 in (1.6 mm) |
| Jacket thickness (nom.) | 0.037 in (0.94 mm) |
| Overall cable diameter (nominal) | 0.198 in (5.03 mm) |
| Bulk cable weight | 17 lbs/1000ft |
| Nom. conductor DCR | 18.2 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 26 pF/ft (85 pF/m) |
| Nom. characteristic impedence | 90 Ohm |
| Nom. inductance | 0.21 µH/ft (0.69 µH/m) |
| Max. current | 2.8 Amps per Conductor at 25ºC |
| Operating temperature | -30°C to +105°C |
| Temperature table notes | AWM 80°C |
| Bend radius (stationary min.) | 2.0 in (51 mm) |
| Bend radius (installation min.) | 2.0 in (51 mm) |
| Max Pull Tension | 18 lbs (8.2 kg) |
| Environmental suitability | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance |
| Flammability / reaction to fire | UL 1685 UL Loading, FT4, T-29-520, IEEE 1202 |
| NEC / UL compliance | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
| AWM compliance | AWM 2464 |
| CEC / C(UL) compliance | CMG |
| European directive compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Item Type | Belden Instrumentation Cable |
| Other Part Numbers | 9407 060100; 9407 060250; 9407 060500; 9407 0601000; 9407 0602500 UPC 612825240099 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.