Belden 9582 002, Multi Conductor Cable 2C 12 AWG PVC, Red Jacket

SKU:Belden 9582 002
$652.80
● In stock
Description
Belden 9582 002 is a 2-conductor fire alarm cable with 12 AWG solid bare copper conductors, PVC insulation, and a red PVC outer jacket. It is designed for riser-rated fire alarm installations with FPLR compliance and a 300 V UL voltage rating. This cable has a nominal overall cable diameter of 0.340 in and is suited for low-voltage signaling and control circuits.
Belden 9582 002 Key Features
- 2 conductors with 12 AWG solid BC - bare copper conductors for fire alarm wiring.
- PVC - polyvinyl chloride insulation with insulation color code: Black, Red.
- Red PVC - polyvinyl chloride jacket with outer shield: No Shield.
- NEC / UL compliance: Article 760, FPLR for riser fire alarm installations.
- UL voltage rating: 300 V for low-voltage signaling and control circuits.
Belden 9582 002 Applications
- Use in fire alarms where riser-rated fire alarm cable is required for system wiring.
- Install in indoor applications in building environments.
- Support low voltage analog signals (4-20ma, 0-10v, ...) for signal transmission in control and monitoring circuits.
- Handle low voltage control (24v, …) for control wiring in low-voltage systems.
Belden™ and all associated trademarks are the property of their respective owners.
Specifications
| Attribute | Value |
|---|---|
| Nom. thickness (insulation) | 0.023 in (0.58 mm) |
| Nom. insulation diameter | 0.127 in (3.23 mm) |
| Nom. thickness (jacket) | 0.042 in (1.1 mm) |
| Nom. diameter (jacket) | 0.34 in |
| Overall cable diameter (nominal) | 0.340 in |
| Nom. conductor DCR | 1.6 Ohm/1000ft |
| Nom. capacitance cond-to-cond | 30 pF/ft (98 pF/m) |
| Nom. inductance | 0.188 µH/ft (0.617 µH/m) |
| Max. current | 21 Amps per Conductor at 25ºC |
| UL temperature | 105°C |
| Operating temperature | -20°C To +75°C |
| Flammability / reaction to fire | UL1666 Riser, FT4, IEC 60332-1-2 |
| Bend radius (stationary min.) | 2.72 in (69.1 mm) |
| Bend radius (installation min.) | 2.72 in |
| Max Pull Tension | 158 lbs (71.7 kg) |
| Bulk cable weight | 70 lbs/1000ft |
| Environmental suitability | Indoor, Outdoor, Sunlight Resistance |
| CPR compliance | CPR Euroclass: Eca |
| CEC / C(UL) compliance | FAS105 |
| European directive compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK regulation compliance | UKCA Mark |
| APAC compliance | China RoHS II (GB/T 26572-2011) |
| Other standard compliance(s) | California State Fire Marshall |
| Item Type | Belden Multi Conductor Cable |
| Other Part Numbers | 9582 002100, 9582 002250, 9582 002500, 9582 0021000, UPC 612825256243 |
| Priced Per | FT |
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?