Southwire 13778699, Armored Cable 1/0 AWG 3C Copper 5 kV 133% / 8 kV 100% Yellow
Southwire · MPN 13778699
Description
Southwire 13778699 is a 1/0 AWG three-conductor medium-voltage armored power cable rated 5 kV 133% / 8 kV 100%. Its three 19-strand copper conductors carry 115 mils of NL-EPR with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 4 AWG bare copper grounding conductor runs with them. Aluminum interlocked armor (AIA) and a yellow SOLONON thermoplastic low smoke zero halogen (LSZH-TP) outer jacket complete the cable.
Southwire 13778699 Technical Specs
Conductors & Insulation
| Conductor Size | 1/0 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 19 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 115 mils (2.92 mm) |
| Diameter Over Conductor | 0.362 in (0.92 cm) |
| Diameter Over Insulation | 0.630 in (1.60 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 0.690 in (1.75 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 4 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Wax paper |
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.862 in (4.73 cm) |
| Outer Jacket | Yellow SOLONON thermoplastic low smoke zero halogen (LSZH-TP) |
| Jacket Thickness | 60 mils (1.52 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.988 in (5.05 cm) |
|---|---|
| Approximate Weight | 2651 lbs/1000 ft (3945 kg/km) |
| Maximum Pull Tension | 2534 lbs (1149.40 kg) |
| Minimum Bend Radius | 13.9 in (35.31 cm) |
Ratings & Compliance
| Voltage Rating | 5 kV 133% / 8 kV 100% |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -25°C |
| Location Rating | Class I and II, Division 2 per NEC Article 501 and 502 |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 1072 Medium-Voltage Power Cables; UL 1685 FT4-ST1 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger); ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE); ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 13778699 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.