Southwire 13818299, Armored Cable 350 KCMIL 3C Copper 25 kV Black
Description
Southwire 13818299 is a 350 KCMIL three-conductor HVTECK armored cable rated 25 kV, 133% insulation level. Its three 37-strand copper conductors carry 320 mils of TR-XLP with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 3 AWG bare copper grounding conductor runs with them. A PVC inner jacket, aluminum interlocked armor (AIA) and a black polyvinyl chloride (PVC) outer jacket complete the cable. The 25kV HVTECK line is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL.
Southwire 13818299 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | Tree-retardant cross-linked polyethylene (TR-XLP) |
| Insulation Thickness | 320 mils (8.13 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
| Diameter Over Insulation | 1.327 in (3.37 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.387 in (3.52 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 3 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Non-wicking, non-hygroscopic, flame retardant polypropylene |
| Binder | Polypropylene tape |
| Inner Jacket | PVC |
| Inner Jacket Thickness | 135 mils (3.43 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 3.660 in (9.30 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 3.830 in (9.73 cm) |
|---|---|
| Approximate Weight | 7895 lbs/1000 ft (11749 kg/km) |
| Maximum Pull Tension | 8400 lbs (3810.17 kg) |
| Minimum Bend Radius | 30.6 in (77.72 cm) |
Ratings & Compliance
| Voltage Rating | 25 kV |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Location Rating | CSA HL rating |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 13818299 Applications
- Industrial and commercial medium voltage installations.
- The line is sunlight and moisture resistant, flame retardant, exceptionally corona resistant and resistant to most chemical soils and acids.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.