Southwire 13862419, Building Wire 1000 kcmil Copper XHHW-2/RW90 White
Description
Southwire 13862419 is a 1000 kcmil copper Type XHHW-2/RW90 building wire in white. Its 61-strand Class B compressed bare copper conductor is insulated with flame-retardant, moisture-resistant thermoset cross-linked polyethylene (XLPE) with patented SIMpull Technology, designed to be installed without pulling lubricant. XHHW-2 is rated 600 volts, or 1000 volts for sizes 8 and larger, and RW90 at 600 volts.
Southwire 13862419 Technical Specs
Construction
| Conductor Size | 1000 kcmil |
|---|---|
| Metric Cross-Section | 507 mm² |
| Conductor Material | Class B compressed stranded bare copper per ASTM B3 and B8 |
| Number of Strands | 61 |
| Insulation | Flame-retardant, moisture-resistant thermoset cross-linked polyethylene (XLPE) with SIMpull Technology |
| Type Designation | XHHW-2/RW90 |
| Insulation Colour | White |
Dimensions and Weight
| Diameter Over Conductor | 1.117 in (2.84 cm) |
|---|---|
| Insulation Thickness | 80 mils (2.03 mm) |
| Approx. Overall Diameter | 1.285 in (3.26 cm) |
| Copper Content Weight | 3087 lbs/1000 ft (4594 kg/km) |
| Approx. Total Weight | 3233 lbs/1000 ft (4811 kg/km) |
Ratings
| XHHW-2 Voltage Rating | 600 volts, or 1000 volts for sizes 8 and larger |
|---|---|
| RW90 Voltage Rating | 600 volts |
| Temperature | Wet or dry locations, not to exceed 90°C |
Features
| Sunlight | Sunlight resistant |
|---|---|
| Cold Bend | -40°C |
| Flame Test | FT1 |
| Oil and Gasoline | Gasoline and Oil Resistant II |
| Cable Tray | CT Rated, 1/0 AWG and larger |
| FT4 | FT4, 350 kcmil and larger |
| RoHS/REACH | Compliant |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger) |
| CSA C22.2 No. 38 | Thermoset-insulated wires and cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202/FT4 | Flame Test (70,000 BTU/hr) 350kcmil and Larger |
| Federal Specification | A-A-59544 |
| NMX-J-451-ANCE | Thermoset insulated wires and cables |
| NOM-063-SCFI | Electrical Products – Conductors – Safety Requirements |
| NEMA 70901-2-2024 | Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire's standards statement for this wire also reads: Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661.
Southwire 13862419 Applications
- Installs in conduit, cable tray or other recognized raceways for services, feeders and branch circuit wiring.
- Type XHHW-2 is suitable for use in health care facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 may be specified.
- Under its RW90 designation it may be used for open wiring, including open wiring exposed to the weather, and in raceways (except cable troughs and ventilated flexible cableways) in dry or wet locations, as per the Canadian Electrical Code.