Southwire 13893099, Armored Cable 3 AWG 2C Copper 1 kV Black
Description
Southwire 13893099 is a 3 AWG two-conductor Type TECK 90 armored cable rated 1 kV. Its two 7-strand copper conductors carry 60 mils of XLPE, and a separate 6 AWG uninsulated grounding conductor runs with them. A PVC inner jacket, aluminum interlocked armor (AIA) and a black low smoke zero halogen (LSZH) outer jacket complete the cable.
Southwire 13893099 Technical Specs
Conductors & Insulation
| Conductor Size | 3 AWG |
|---|---|
| Number of Conductors | 2 |
| Strands per Conductor | 7 |
| Conductor | Class B stranded copper, compressed or compact, per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation Thickness | 60 mils (1.52 mm) |
| Conductor Colors | Black, white |
| Diameter Over Conductor | 0.247 in (0.63 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 6 AWG uninsulated Class B stranded grounding conductor |
|---|---|
| Inner Jacket | Black polyvinyl chloride (PVC) |
| Inner Jacket Thickness | 85 mils (2.16 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.239 in (3.15 cm) |
| Outer Jacket | Black low smoke zero halogen (LSZH) |
| Jacket Thickness | 45 mils (1.14 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.329 in (3.38 cm) |
|---|---|
| Approximate Weight | 911 lbs/1000 ft (1356 kg/km) |
| Maximum Pull Tension | 842 lbs (381.92 kg) |
| Minimum Bend Radius | 9.3 in (23.62 cm) |
Ratings & Compliance
| Voltage Rating | 1 kV |
|---|---|
| Type Designation | Type TECK 90 |
| Operating Temperatures | 90°C maximum continuous operating; -25°C minimum installation; -40°C CSA cold bend and impact |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Sunlight Resistance | Sunlight resistant |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 131 Type TECK 90 Cable; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA ST1 Smoke Test - marked FT4-ST1; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; CSA AG14 - Acid Gas Compliance; IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems |
Southwire 13893099 Applications
- Exposed or concealed wiring in wet or dry locations.
- Ventilated, non-ventilated and ladder-type cable troughs and ventilated flexible cableway, in wet, dry or classified locations.
- Control, lighting and power circuits in pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.