Southwire 20494105 is a 6 AWG copper building wire in white, designated SIMpull THHN-THWN-2 MTW-AWM. Its 19-strand conductor is combination-unilay stranded, soft drawn annealed bare copper, insulated with heat and moisture resistant PVC under a nylon jacket utilizing SIMpull Technology, and is designed to be installed without the application of a pulling lubricant. Rated 600 volts for all applications.
Southwire 20494105 Technical Specs
Construction
| Conductor Size | 6 AWG |
|---|---|
| Conductor | Combination-unilay stranded soft drawn annealed bare copper per ASTM B787 |
| Number of Strands | 19 |
| Stranding Class | Class C (sizes 8 - 2) |
| Insulation | Heat and moisture resistant PVC |
| Sheath | Nylon, utilizing SIMpull Technology |
| Type Designation | THHN-THWN-2 MTW-AWM |
| Insulation Colour | White |
Dimensions and Weight
| Diameter Over Conductor | 0.179 in (0.45 cm) |
|---|---|
| Insulation Thickness | 31 mils (0.79 mm) |
| Nylon Sheath Thickness | 6 mils (0.15 mm) |
| Approx. Overall Diameter | 0.253 in (0.64 cm) |
| Copper Content Weight | 81 lbs/1000 ft (121 kg/km) |
| Approx. Total Weight | 95 lbs/1000 ft (141 kg/km) |
Ratings
| Voltage | 600 volts, all applications |
|---|---|
| THHN | Dry locations not to exceed 90°C |
| THWN-2 | Wet or dry locations not to exceed 90°C, or 75°C when exposed to oil |
| MTW | Wet locations or exposed to oil, not to exceed 60°C; dry locations not to exceed 90°C (ampacity limited to that for 75°C conductor temperature per NFPA 79); stranded constructions only |
| AWM | Dry locations not to exceed 105°C only when rated and used as appliance wiring material (sizes 14 through 6 AWG) |
Features
| Sunlight | Sunlight resistant, #8 AWG and larger |
|---|---|
| Oil and Gasoline | Gasoline and Oil Resistant II |
| VW-1 | All sizes |
| FT-1 | All sizes |
| RoHS | Compliant |
Standards
| ASTM B787 | 19 Wire Combination Unilay-Stranded Copper Conductors |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 758 | Standard for Appliance Wiring Material |
| UL 1063 | Machine Tool Wiring (MTW) |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| Federal Specification | A-A-59544 |
| NMX-J-010-ANCE | Thermoplastic insulated wires and cables |
| NOM-063-SCFI | Electrical Products – Conductors – Safety Requirements |
| NEMA 70901-2-2024 | Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire 20494105 Applications
- Pulled in conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications, as specified in the National Electrical Code and other applicable codes and standards.
- Machine tool wiring falls under its MTW designation.