Southwire 21810798, Building Wire 2 AWG Copper SIMpull XHHW-2/RW90 White
Description
Southwire 21810798 is a 2 AWG single-conductor copper building wire with white SIMpull XHHW-2/RW90 insulation. Its 7-strand Class B compressed stranded bare copper conductor, per ASTM B3 and B8, is insulated with flame-retardant, moisture-resistant thermoset cross-linked polyethylene (XLPE) with Southwire's patented SIMpull Technology. XHHW-2 is rated 600 volts, or 1000 volts for sizes 8 and larger, and RW90 at 600 volts.
Southwire 21810798 Technical Specs
Conductor
| Conductor Size | 2 AWG |
|---|---|
| Metric Size | 33.6 mm² |
| Number of Conductors | 1 |
| Conductor | Class B compressed stranded bare copper |
| Number of Strands | 7 |
| Diameter Over Conductor | 0.282 in (0.72 cm) |
Insulation
| Type | XHHW-2/RW90 |
|---|---|
| Insulation | Thermoset cross-linked polyethylene (XLPE), flame-retardant and moisture-resistant |
| Insulation Colour | White |
| Insulation Thickness | 45 mils (1.14 mm) |
Dimensions and Weight
| Approx. Overall Diameter | 0.379 in (0.96 cm) |
|---|---|
| Copper Content Weight | 204 lbs/1000 ft (304 kg/km) |
| Approx. Total Weight | 228 lbs/1000 ft (339 kg/km) |
Ratings
| Max. Conductor Temperature | 90°C, wet or dry locations |
|---|---|
| Voltage, XHHW-2 | 600 volts, or 1000 volts for sizes 8 AWG and larger |
| Voltage, RW90 | 600 volts |
Compliance
| Standards | ASTM B3, ASTM B8, UL 44, CSA C22.2 No. 38, ICEA S-95-658 (NEMA WC70), Federal Specification A-A-59544, NMX-J-451-ANCE, NOM-063-SCFI |
|---|
Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661; and NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable.
Southwire 21810798 Applications
- Services, feeders and branch-circuit wiring installed in conduit, cable tray or other recognized raceways.
- Pulls without lubricant: SIMpull XHHW-2/RW90 conductors install without one.
- Health care facilities: Type XHHW-2 is suitable there per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 may be specified.
- Under the Canadian Electrical Code, RW90 suits open wiring, including open wiring exposed to the weather, and raceways other than cable troughs and ventilated flexible cableways, in dry or wet locations.
- Features: sunlight resistant; -40°C cold bend; FT1; Gasoline and Oil Resistant II; RoHS/REACH compliant.