Southwire 22972401, Building Wire 12 AWG Stranded Copper THHN-THWN-MTW-AWM Gray
Description
Southwire 22972401 is a 12 AWG stranded copper building wire with gray insulation, carrying the THHN-THWN-MTW-AWM type designation. Its 19-strand Class C combination-unilay conductor is soft drawn annealed bare copper, insulated with heat- and moisture-resistant PVC under a nylon sheath. The voltage is 600 volts for all applications.
Southwire 22972401 Technical Specs
Conductor & Construction
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 1 |
| Conductor | Class C combination-unilay soft drawn annealed bare copper per ASTM B787 |
| Number of Strands | 19 |
| Insulation | Heat and moisture resistant PVC |
| Sheath | Nylon |
| Insulation Colour | Gray |
| Type Designation | THHN-THWN-MTW-AWM |
Dimensions & Weight
| Diameter Over Conductor | 0.090 in (0.23 cm) |
|---|---|
| Insulation Thickness | 16 mils (0.41 mm) |
| Nylon Sheath Thickness | 5 mils (0.13 mm) |
| Approx. Overall Diameter | 0.132 in (0.34 cm) |
| Copper Content Weight | 20 lbs/1000 ft (30 kg/km) |
| Approx. Total Weight | 25 lbs/1000 ft (37 kg/km) |
Ratings
| Voltage | 600 V, all applications |
|---|---|
| THHN | Dry locations not to exceed 90°C |
| THWN | Wet locations not to exceed 75°C; dry locations not to exceed 90°C; 75°C when exposed to oil |
| MTW | Wet locations or exposed to oil, not to exceed 60°C; dry locations not to exceed 90°C (ampacity limited to that for 75°C conductor temperature per NFPA 79) |
| AWM | Dry locations not to exceed 105°C, only when rated and used as appliance wiring material |
Features
| Oil and Gasoline | Gasoline and Oil Resistant II |
|---|---|
| VW-1 | Sizes 14 through 10 AWG |
| FT1 | All sizes |
| RoHS | Compliant |
Standards
| ASTM B787 | 19 Wire Combination Unilay-Stranded Copper Conductors |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 758 | Standard for Appliance Wiring Material |
| UL 1063 | Machine Tool Wiring (MTW) |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| Federal Specification | A-A-59544 |
| NMX-J-010-ANCE | Thermoplastic insulated wires and cables |
| NOM-063-SCFI | Electrical Products – Conductors – Safety Requirements |
| NEMA 70901-2-2024 | Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire 22972401 Applications
- These THHN conductors are primarily for conduit runs on branch circuits in commercial or industrial work, as set out in the National Electrical Code and other applicable codes and standards.
- The AWM designation allows use as appliance wiring material where the wire is rated and used as such.
- Machine tool wiring is covered by the MTW designation, which is limited to stranded constructions.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.