Southwire 25659467, Building Wire 10 AWG Stranded Copper THHN/THWN MTW AWM Purple
Description
Southwire 25659467 is a 10 AWG single-conductor copper building wire in purple, with 19-strand construction and THHN/THWN, MTW and AWM type designations. It is built with PVC insulation and a nylon sheath, and it is rated 600 volts.
Southwire 25659467 Technical Specs
Conductor & Dimensions
| Conductor Size | 10 AWG |
|---|---|
| Conductor Material | Copper |
| Number of Conductors | 1 |
| Strands | 19 |
| Conductor | Stranded Class C combination-unilay, soft drawn annealed bare copper per ASTM B787 |
| Diameter Over Conductor | 0.117 in (0.30 cm) |
| Insulation | Heat- and moisture-resistant PVC insulation with a nylon sheath |
| Insulation Thickness | 20 mils (0.51 mm) |
| Nylon Sheath Thickness | 5 mils (0.13 mm) |
| Approx. Outside Diameter | 0.165 in (0.42 cm) |
| Copper Weight | 32 lbs/1000 ft (48 kg/km) |
| Approx. Weight | 39 lbs/1000 ft (58 kg/km) |
| Insulation Colour | Purple |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designations | THHN/THWN, MTW, AWM |
| THHN Temperature | Dry locations, not to exceed 90°C |
| THWN Temperature | Wet locations, not to exceed 75°C; dry locations, not to exceed 90°C; not to exceed 75°C when exposed to oil |
| MTW Temperature | Wet locations or exposed to oil, not to exceed 60°C; dry locations, not to exceed 90°C (ampacity limited to that for 75°C conductor temperature per NFPA 79) |
| AWM Temperature | Dry locations, not to exceed 105°C, only when rated and used as appliance wiring material |
| Features | Gasoline and Oil Resistant II; VW-1, sizes 14 through 10 AWG; FT1, all sizes; RoHS compliant |
Compliance & Standards
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors; UL 83 Thermoplastic Insulated Wires and Cables; UL 758 Standard for Appliance Wiring Material; UL 1063 Machine Tool Wiring (MTW); CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables; ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy; Federal Specification A-A-59544; NMX-J-010-ANCE Thermoplastic insulated wires and cables; NOM-063-SCFI Electrical Products – Conductors – Safety Requirements |
|---|---|
| Domestic Preference | NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire 25659467 Applications
- Installed in conduit for branch circuits in commercial or industrial buildings, as specified in the National Electrical Code and other applicable codes and standards.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.