Southwire 26069507, Building Wire 6 AWG Copper THHN-THWN-2 MTW-AWM Brown
Description
Southwire 26069507 is a 6 AWG single-conductor SIMpull THHN-THWN-2 building wire with MTW and AWM designations, in brown. Its 19-strand combination-unilay soft drawn annealed bare copper conductor carries heat and moisture resistant PVC insulation under a nylon sheath applied with SIMpull Technology. Rated 600 volts, and the conductor is designed to be installed without a pulling lubricant.
Southwire 26069507 Technical Specs
Construction
| Conductor Size | 6 AWG |
|---|---|
| Number of Conductors | 1 |
| Strands | 19 |
| Conductor | Combination-unilay stranded soft drawn annealed bare copper per ASTM B787 |
| Insulation | Heat and moisture resistant PVC |
| Sheath | Nylon, with SIMpull Technology |
| Insulation Colour | Brown |
Dimensions and Weight
| Diameter Over Conductor | 0.179 in (0.45 cm) |
|---|---|
| Insulation Thickness | 31 mils (0.79 mm) |
| Nylon Sheath Thickness | 6 mils (0.15 mm) |
| Approx. Outside Diameter | 0.253 in (0.64 cm) |
| Copper Weight | 81 lbs/1000 ft (121 kg/km) |
| Approx. Total Weight | 95 lbs/1000 ft (141 kg/km) |
Ratings
| Voltage | 600 volts |
|---|---|
| THHN | Dry locations, not to exceed 90°C |
| THWN-2 | Wet or dry locations, not to exceed 90°C; 75°C when exposed to oil |
| MTW | Wet locations or exposed to oil, not to exceed 60°C; dry locations, not to exceed 90°C, with ampacity limited to that for 75°C conductor temperature per NFPA 79 |
| AWM | Dry locations, not to exceed 105°C, only when rated and used as appliance wiring material |
| Stranding Class | Class C (sizes 8 - 2) |
| Sunlight Resistance | Sunlight resistant, #8 AWG and larger |
| Flame Tests | VW-1 All Sizes; FT-1 All Sizes |
| Oil and Gasoline | Gasoline and Oil Resistant II |
| RoHS | RoHS Compliant |
Standards
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
|---|---|
| ASTM B787 | 19 Wire Combination Unilay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 758 | Standard for Appliance Wiring Material |
| UL 1063 | Machine Tool Wiring (MTW) |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| Federal Specification | A-A-59544 |
| NMX-J-010-ANCE | Thermoplastic insulated wires and cables |
| NOM-063-SCFI | Electrical Products – Conductors – Safety Requirements |
| NEMA 70901-2-2024 | Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable |
Southwire 26069507 Applications
- Runs in conduit for services, feeders and branch circuits in commercial or industrial installations, as specified in the National Electrical Code and other applicable codes and standards.
- These conductors carry multiple ratings depending upon the product application, so one wire can serve THHN, THWN-2, MTW and AWM duties within the limits above.
- Pulls into raceway without a pulling lubricant, which the SIMpull sheath allows.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.