Southwire 40855999, Control Tray Cable 12 AWG 4C Copper THHN TC-ER 600V Black
Description
Southwire 40855999 is a 12 AWG 4-conductor control tray cable with bare copper conductors, PVC-with-nylon Type THHN or THWN insulation (VW-1 rated) and a black PVC jacket. It is Type TC-ER and rated 600V.
Southwire 40855999 Technical Specs
Construction
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 4 |
| Conductor | 7-strand Class B compressed bare copper per ASTM B3 and B8 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer, Type THHN or THWN, VW-1 rated |
| Conductor Identification | Black, Red, Blue, Orange (ICEA S-58-679 Method 1, Table 2) |
| Filler | Polypropylene |
| Jacket | Black polyvinyl chloride (PVC) |
| Type Designation | TC-ER |
Dimensions and Weight
| Insulation Thickness | 20 mils (0.51 mm) |
|---|---|
| Jacket Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.401 in (1.02 cm) |
| Minimum Bend Radius | 1.6 in (4.06 cm) |
| Copper Weight | 81 lbs/1000 ft (121 kg/km) |
| Approx. Total Weight | 149 lbs/1000 ft (222 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 75°C wet, 90°C dry; 105°C emergency overload; 250°C short circuit |
| DC Resistance at 25°C | 1.662 |
| AC Resistance at 75°C | 2.002 |
| Allowable Ampacity, Raceway, 75°C | 20 |
| Allowable Ampacity, Raceway, 90°C | 24 |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 1 Table 2 |
| ICEA S-73-532 | Control, Thermocouple Extension and Instrumentation Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 40855999 Applications
- Wet and dry locations, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Class I, II and III, Division 2 per NEC Articles 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.