Southwire 45680601, Armored Cable 500 KCMIL 3C Copper 25 kV Red
Southwire · MPN 45680601
Description
Southwire 45680601 is a 500 KCMIL three-conductor HVTECK armored cable rated 25 kV, 100% insulation level. Its three 37-strand copper conductors carry 260 mils of NL-EPR with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 3 AWG bare copper grounding conductor runs with them. A PVC inner jacket, aluminum interlocked armor (AIA) and a red polyvinyl chloride (PVC) outer jacket complete the cable. The 25kV HVTECK line is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL.
Southwire 45680601 Technical Specs
Conductors & Insulation
| Conductor Size | 500 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 260 mils (6.60 mm) |
| Insulation Level | 100% |
| Diameter Over Conductor | 0.766 in (1.95 cm) |
| Diameter Over Insulation | 1.332 in (3.38 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.392 in (3.54 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 3 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Non-wicking fillers in the interstices |
| Binder | Polypropylene tape |
| Inner Jacket | PVC |
| Inner Jacket Thickness | 135 mils (3.43 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 3.670 in (9.32 cm) |
| Outer Jacket | Red polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 3.840 in (9.75 cm) |
|---|---|
| Approximate Weight | 9440 lbs/1000 ft (14048 kg/km) |
| Maximum Pull Tension | 12000 lbs (5443.10 kg) |
| Minimum Bend Radius | 26.8 in (68.07 cm) |
Ratings & Compliance
| Voltage Rating | 25 kV |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Location Rating | CSA HL rating |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 45680601 Applications
- Industrial and commercial medium voltage installations.
- The line is sunlight and moisture resistant, flame retardant, exceptionally corona resistant and resistant to most chemical soils and acids.