Southwire 45737999, Armored Cable 750 KCMIL 3C Copper 15 kV Red
Southwire · MPN 45737999
Description
Southwire 45737999 is a 750 KCMIL three-conductor medium-voltage ARMOR-X® armored power cable rated 15 kV, 133% insulation level. Its three 61-strand copper conductors carry 220 mils of NL-EPR with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 1/0 AWG bare copper grounding conductor runs with them. ARMOR-X® continuous corrugated welded aluminum armor and a red polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 45737999 Technical Specs
Conductors & Insulation
| Conductor Size | 750 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 61 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 220 mils (5.59 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.968 in (2.46 cm) |
| Diameter Over Insulation | 1.464 in (3.72 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.524 in (3.87 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 1/0 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Wax paper |
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded aluminum armor |
| Diameter Over Armor | 3.850 in (9.78 cm) |
| Outer Jacket | Red polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 4.028 in (10.23 cm) |
|---|---|
| Approximate Weight | 12115 lbs/1000 ft (18029 kg/km) |
| Maximum Pull Tension | 18000 lbs (8164.66 kg) |
| Minimum Bend Radius | 28.2 in (71.63 cm) |
Ratings & Compliance
| Voltage Rating | 15 kV |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -50°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; ASTM B496 Compact Round Concentric-lay-standard copper; UL 1072 Medium-Voltage Power Cables; UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; UL 2225 Cables and Cable-Fittings For Use In Classified Locations; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 45737999 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.