Description
Southwire 45815801 is a SIMpull MC-PCS Duo™ Type MC cable with a power element and a signal element under one lightweight interlocked armor. The power element is two 12 AWG solid copper THHN/THWN conductors, brown and gray, with a green insulated ground. The signal element is a pair of 16 AWG solid copper Type TFN singles, purple and pink, under their own light blue jacket; those colors belong to the pair, not to the cable.
Southwire 45815801 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Power Conductors | 2, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Conductor Colors | Brown, Gray |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
| Signal Pair | Two 16 AWG solid copper Type TFN insulated singles, purple and pink, under an overall light blue jacket |
Grounding and Armor
| Ground | Green polyvinyl chloride with nylon sheath Type THHN/THWN insulated ground conductor |
|---|---|
| Ground Size | 1x12 |
| Binder | Mylar tape; binder tape with print legend wrapped around the assembly |
| Armor | Lightweight interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.590 in (1.50 cm) |
|---|---|
| Approximate Weight | 164 lbs per 1,000 ft (244 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry (Type THHN/THWN) |
|---|---|
| Location | Dry, indoor locations only per NEC 330.10(A)(10) (unjacketed) |
Standards and Compliance
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 45815801 Applications
- Branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- LED lighting with 0-10V dimming, with power and control/signal conductors under one armor.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Installs without anti-short bushings.