Southwire 47212606, Building Wire 10 AWG Stranded Copper T90/TWN75/THHN/THWN Red
Description
Southwire 47212606 is a 10 AWG single-conductor building wire in red, with 19-strand combination unilay copper and PVC insulation with a nylon sheath. It carries the T90/TWN75/THHN/THWN type designations and a maximum voltage rating of 600 volts.
Southwire 47212606 Technical Specs
Conductor & Dimensions
| Conductor Size | 10 AWG |
|---|---|
| Conductor Material | Copper |
| Number of Conductors | 1 |
| Strands | 19 |
| Conductor | Combination unilay-stranded copper per ASTM B787 |
| Diameter Over Conductor | 0.117 in (0.30 cm) |
| Insulation | Polyvinyl chloride (PVC) with nylon sheath |
| Insulation Thickness | 20 mils (0.51 mm) |
| Insulation Colour | Red |
| Approx. Outside Diameter | 0.165 in (0.42 cm) |
| Copper Weight | 32 lbs/1000 ft (48 kg/km) |
| Approx. Weight | 38 lbs/1000 ft (57 kg/km) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designations | T90, TWN75, THHN, THWN |
| T90 Nylon Temperature | Dry locations, not exceeding 90°C |
| TWN75 Temperature | Wet or dry locations, not more than 75°C |
| Minimum Installation Temperature | -25°C |
| Minimum Operating Temperature | -40°C |
| Silicone Free | Non-SIMpull silicone-free construction, sizes 14, 12 and 10 AWG |
Compliance & Standards
| Standards | ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors; CSA FT-1 Flame Test; Canadian Electrical Code |
|---|
Southwire 47212606 Applications
- As T90 Nylon, intended for installation in conduit (raceways) as exposed wiring in dry locations.
- Its TWN75 designation covers wet or dry locations within the 75°C limit given above.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.