Southwire 50602201, Bare Aluminum Conductor ACSS 636 KCMIL 26/7 GROSBEAK
Description
Southwire 50602201 is an ACSS bare conductor in 636 KCMIL, codeword GROSBEAK: 26 strands of fully annealed, soft-temper aluminum 1350-O over a steel core of 7 wires, which carries most or all of the conductor's mechanical load. It measures 990 mils nominal outside diameter and 874 lbs per 1000 ft.
Southwire 50602201 Technical Specs
Conductor
| Codeword | GROSBEAK |
|---|---|
| Conductor Type | ACSS (Aluminum Conductor, Steel Supported) |
| Southwire Designation | 636-26/7 ACSS/MA2/63% GROSBEAK |
| Conductor Size | 636 KCMIL |
| Stranding (Aluminum/Steel) | 26/7 |
| Aluminum Wire | 1350-O, fully annealed (soft) temper |
| Core Designation | MA2 |
| Steel Core Coating | Zinc-5% aluminum-mischmetal alloy |
Dimensions and Weight
| Nominal Outside Diameter | 990 mils (25.16 mm) |
|---|---|
| Nominal Total Weight | 874 lbs/1000 ft (1301 kg/km) |
Standards
| ASTM B500 | Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors |
|---|---|
| ASTM B609 | Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes |
| ASTM B802 | Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR) |
| ASTM B803 | High-Strength Zinc-5% Aluminum Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors |
| ASTM B856 | Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS) |
| ASTM B958 | Extra-High-Strength and Ultra-High-Strength Class A Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors |
Southwire 50602201 Applications
- Overhead distribution and transmission lines.
- The line operates continuously at temperatures up to 250°C without loss of strength.
- Compared with a comparable ACSR, it sags less under electrical loadings; final sags are not affected by long-term creep, and it is self-damping when prestretched during installation.
- Reconductoring for increased current with existing tensions and clearances, new lines where reduced sag economizes structures or high emergency loadings are required, and lines with aeolian vibration problems.
- Corrosion protection should be chosen to suit the environment of the installation.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.