Southwire 55058689, Armored Cable 14 AWG 3C Copper XHHW-2 600 V Black
Southwire · MPN 55058689
Description
Southwire 55058689 is a 14 AWG three-conductor Type MC-HL ARMOR-X® armored cable rated 600 V. Its three 7-strand copper conductors carry 30 mils of XHHW-2 XLPE, and three 18 AWG bare copper grounding conductors run with them. ARMOR-X® continuous corrugated welded armor and a black polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 55058689 Technical Specs
Conductors & Insulation
| Conductor Size | 14 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 7 |
| Conductor | Class B compressed copper, 7 strands, per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 30 mils (0.76 mm) |
| Conductor Colors | Black 1, red 2, blue 3 |
Grounding, Armor & Jacket
| Grounding Conductors | Three 18 AWG Class B compressed stranded bare copper grounding conductors |
|---|---|
| Filler | Polypropylene |
| Armor | ARMOR-X® continuous corrugated welded armor |
| Diameter Over Armor | 0.530 in (1.35 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 50 mils (1.27 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 0.636 in (1.62 cm) |
|---|---|
| Approximate Weight | 191 lbs/1000 ft (284 kg/km) |
| Copper Weight | 53 lbs/1000 ft (79 kg/km) |
| Minimum Bend Radius | 4.5 in (11.43 cm) |
Electrical Characteristics
| DC Resistance at 25 °C | 2.631 |
|---|---|
| AC Resistance at 75 °C | 3.170 |
| Allowable Ampacity in Raceway, 75 °C | 20 |
| Allowable Ampacity in Raceway, 90 °C | 25 |
Ratings & Compliance
| Voltage Rating | 600 V |
|---|---|
| Type Designation | Type MC-HL; CSA RA90-HL |
| Operating Temperatures | 90°C normal operation; 130°C emergency overload; 250°C short circuit |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 44 Thermoset-Insulated Wires and Cables; UL 1569 Metal-Clad Cables; UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test; UL 2225 Cables and Cable-Fittings For Use In Classified Locations; CSA C22.2 No. 123 Metal Sheathed Cables; CSA C22.2 No. 174; ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2; ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables; ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy; ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors (3 conductor constructions only); IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr) |
Southwire 55058689 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.