Southwire 55061999, Armored Cable 12 AWG 11C Copper XHHW-2 600 V Black
Description
Southwire 55061999 is a 12 AWG, 11-conductor Type MC-HL armored control cable rated 600 V. Its eleven 7-strand compressed copper conductors carry 30 mils of XHHW-2 cross-linked polyethylene (XLPE), with one 12 AWG green-insulated copper grounding conductor alongside. ARMOR-X® continuous corrugated welded aluminum armor and a black PVC outer jacket complete the cable.
Southwire 55061999 Technical Specs
Conductors & Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 11 |
| Strands per Conductor | 7 |
| Conductor | Class B compressed copper, 7 strands, per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 30 mils (0.76 mm) |
| Conductor Colors | Black, red, blue, orange, yellow, brown, red-black stripe, blue-black stripe, orange-black stripe, yellow-black stripe, brown-black stripe |
Grounding, Armor & Jacket
| Grounding Conductor | One 12 AWG Class B compressed stranded copper with green insulation |
|---|---|
| Filler | Polypropylene, as needed |
| Binder | Polyester flat thread binder tape, as needed |
| Armor | ARMOR-X® continuous corrugated welded aluminum armor |
| Diameter Over Armor | 0.920 in (2.34 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 50 mils (1.27 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.026 in (2.61 cm) |
|---|---|
| Approximate Weight | 516 lbs/1000 ft (768 kg/km) |
| Copper Weight | 243 lbs/1000 ft (362 kg/km) |
| Minimum Bend Radius | 7.2 in (18.29 cm) |
Electrical Characteristics
| DC Resistance at 25°C (ohms/1000 ft) | 1.662 |
|---|---|
| AC Resistance at 75°C (ohms/1000 ft) | 2.002 |
| Allowable Ampacity in Raceway, 75°C | 12 |
| Allowable Ampacity in Raceway, 90°C | 15 |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designation | Type MC-HL |
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Cold Bend | -40°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1569 Metal-Clad Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 2225 Cables and Cable-Fittings For Use In Classified Locations
- ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
- ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
Southwire 55061999 Applications
- Wet and dry areas, conduits, ducts, troughs and trays.
- Direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.