Southwire 55081701, Galflex RWS Steel Flexible Conduit 3/8 Inch
Southwire · MPN 55081701
Description
Southwire 55081701 is Galflex® Type RWS (Reduced Wall Steel) flexible metal conduit in the 3/8" trade size. A galvanized, corrosion-resistant, high-strength steel alloy strip is helically formed into continuously interlocked conduit that withstands impact and crushing forces, finished with a hot-dipped, heavy zinc coating for rust and corrosion resistance.
Galflex Type RWS meets or exceeds the following requirements: UL Listed per UL 1, Standard for Safety for Flexible Metal Conduit; federal specification WW-C-566c; and REACH/RoHS-2 (Chemical Limit). Its NEC Type designation is Article 348, Type FMC (flexible metal conduit), and its UL product category is DXUZ.
Southwire 55081701 Technical Specs
Dimensions
| Trade Size | 3/8" |
|---|---|
| Inside Diameter | 0.375 in (0.95 cm) |
| Outside Diameter (approx.) | 0.560 in (1.42 cm) |
| Minimum Bend Radius | 2.0 in (5.08 cm) |
| Weight (approx.) | 19 lbs/1000 ft (28 kg/km) |
Construction
| Material | Galvanized, high-strength steel alloy |
|---|---|
| Form | Helically formed, continuously interlocked metal strip |
| Coating | Hot-dipped, heavy zinc |
Standards
| Standards | UL 1; CSA 22.2 No. 56; NFPA 70 (NEC) Article 348 |
|---|
Southwire 55081701 Applications
- Acts as a metal raceway for wires and cables per NEC (ANSI/NFPA-70) Article 348, in concealed or exposed installations.
- Carries power and lighting branch-circuit conductors and cables connecting receptacles, luminaires, equipment and office partitions, along with motor feeder, branch and control circuit conductors and cables.
- Houses Class 1, Class 2 and Class 3 remote-control, signaling and power-limited circuit conductors, fire alarm conductors of power-limited or non-power-limited circuits, and voice, data, communications and video cables including CATV and optical fiber.
- Used for environmental air-handling spaces per NEC 300.22(C), elevators, hoistways and escalators per NEC 620.21, and cranes and hoists per NEC 610.11(C).
- Connects listed wired fixtures per NEC 410.77(C) and information technology equipment under raised floors per NEC 645.5(D)(2) and 645.5(D).
- Feeds electric signs and outline lighting per NEC 600.7, 600.31 (1000 volts or less) and 600.32 (>1000 volts).
- May serve as a grounding conductor for lengths up to 6 feet (20A max) as per NEC 250.118(5).
- Class 1, Div. 2, for flexible connectors only per NEC 501.10(B)(2) & 501.30(B).
- Appears in UL 1, 2, & 3 Hour Through-Penetration Firestop Systems C-AJ-1462, C-AJ-1463, C-AJ-1464, W-L-1308 and W-L-1309.