Southwire 55082702, Titan2 Type UL Liquidtight Flexible Conduit 3/4 Inch Gray
Description
Southwire 55082702 is Titan2™ Type UL liquidtight flexible metal conduit in the 3/4" trade size, with a gray jacket. Its core is a spiral-wound strip of heavy-gauge, corrosion-resistant, hot-dipped galvanized steel; for 3/8" through 1-1/4" trade sizes, the core is constructed with a square-locked steel strip with an integral copper-bonding strip enclosed within the steel convolutions. A rugged, flame-retardant flexible PVC jacket is extruded over the steel core and protects against liquids, oil, certain chemicals, temperature, extreme weather and sunlight.
Southwire 55082702 Technical Specs
Dimensions
| Trade Size | 3/4" |
|---|---|
| Inside Diameter | 0.820 in (2.08 cm) |
| Outside Diameter (approx.) | 1.030 in (2.62 cm) |
| Minimum Bend Radius | 8.5 in (21.59 cm) |
| Weight (approx.) | 38 lbs/1000 ft (57 kg/km) |
Construction
| Core | Spiral-wound, hot-dipped galvanized steel strip |
|---|---|
| Jacket | Flame-retardant flexible PVC |
| Jacket Color | Gray |
Standards
| Standards | UL 360; CSA 22.2 No. 56; NFPA 70 (NEC) Article 350 |
|---|
Southwire 55082702 Applications
- Installs and protects electrical conductors in circuits of 600 Volts nominal, or less, including in extreme temperature environments.
- Fits installations where operation or maintenance calls for flexibility or protection from liquids, vapors, solids or weather, whether exposed or concealed, including runs that need movement, crossover connections or tight bends.
- Serves conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment in industrial and commercial settings.
- Permitted for equipment grounding in sizes 3/8" through 1-1/4" in lengths not exceeding 6 feet per NEC 250.118(6).
- Rated for direct burial applications including concrete encasement.
- Makes flexible connections to swimming pool, spa and hot tub motors per NEC 680.21(A)(3) & 680.42(A)(1), and carries electric sign and outline lighting supply and secondary-circuit conductors per NEC 600.7, 600.31 (1000 volts or less) & 600.32 (over 1000 volts).
- Covers floating building feeders and services per NEC 553.7, boatyards and marinas per NEC 555.13, cranes and hoists per NEC 610.11(C), and elevators, dumbwaiters, escalators, moving walks, wheelchair lifts and stairway chair lifts per NEC 620.21 (where expressly permitted).
- Under raised floors, it carries information technology equipment conductors and cables per NEC 645.5 (D) & 645.5(D)(2); for service entrance it is used in lengths up to six feet per NEC 230.43(15).
- Class I, Div. 2 (NEC 501.10(B)(2) and 501.30(B)); Class II, Div. 1 and 2 (NEC 502.10(A)(2), 502.30(B) and 502.10(B)(2)); Class III, Div. 1 and 2 (NEC 503.10(A)(2) and 503.30(B)).
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.