Southwire 55085699, Armored Cable 4/0 AWG 4C Copper XHHW-2 600 V Black
Southwire · MPN 55085699
Description
Southwire 55085699 is a 4/0 AWG, four-conductor Type MC-HL armored power cable rated 600 V. Its 19-strand compressed bare copper conductors carry 55 mils of XHHW-2 cross-linked polyethylene (XLPE), with one 4 AWG bare copper grounding conductor. ARMOR-X® continuous corrugated welded armor and a black thermoplastic SOLONON low smoke zero halogen (LSZH-TP) outer jacket complete the cable.
Southwire 55085699 Technical Specs
Conductors & Insulation
| Conductor Size | 4/0 AWG |
|---|---|
| Number of Conductors | 4 |
| Strands per Conductor | 19 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and B8 |
| Diameter Over Conductor | 0.512 in (1.30 cm) |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 55 mils (1.40 mm) |
| Conductor Colors | Black (1), red (2), blue (3), orange (4) |
Grounding, Armor & Jacket
| Grounding Conductor | One 4 AWG Class B compressed stranded bare copper |
|---|---|
| Filler | Paper |
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded armor |
| Diameter Over Armor | 1.845 in (4.69 cm) |
| Outer Jacket | Black thermoplastic SOLONON low smoke zero halogen (LSZH-TP) |
| Jacket Thickness | 60 mils (1.52 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.965 in (4.99 cm) |
|---|---|
| Approximate Weight | 3541 lbs/1000 ft (5270 kg/km) |
| Maximum Pull Tension | 5416 lbs (2456.65 kg) |
| Minimum Bend Radius | 13.8 in (35.05 cm) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designation | Type MC-HL |
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Cold Bend | -40°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1569 Metal-Clad Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 2225 Cables and Cable-Fittings For Use In Classified Locations
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
Southwire 55085699 Applications
- Wet and dry areas, conduits, ducts, troughs and trays.
- Direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.