Southwire 55091907, Galflex RWS Steel Flexible Conduit 2 Inch
Description
Southwire 55091907 is Galflex® Type RWS (Reduced Wall Steel) flexible metal conduit in the 2" trade size. A strip of galvanized, corrosion-resistant, high-strength steel alloy is helically formed into a continuously interlocked raceway that withstands impact and crushing forces and gives mechanical protection to the conductors and cables pulled through it.
Galflex Type RWS meets or exceeds the following: UL Listed per UL 1, Standard for Safety for Flexible Metal Conduit, ANSI/UL-1; federal specification WW-C-566c; NEC Type Designation Article 348, Type FMC (flexible metal conduit); UL Product Category DXUZ; and REACH/RoHS-2 (Chemical Limit) compliance. It is intended for use with listed connectors for NEC Type FMC. It has a smooth interior for easy wire pulling, high-strength steel construction, superior crush-proof qualities, a hot-dipped, heavy zinc coating for rust and corrosion resistance, and built-in flexibility for simplified positioning.
Southwire 55091907 Technical Specs
Dimensions
| Trade Size | 2" |
|---|---|
| Inside Diameter | 2.00 in (5.08 cm) |
| Outside Diameter (approx.) | 2.35 in (5.97 cm) |
| Minimum Bend Radius | 10.0 in (25.40 cm) |
| Weight (approx.) | 133 lbs/1000 ft (198 kg/km) |
Construction
| Material | Galvanized, corrosion-resistant, high-strength steel alloy |
|---|---|
| Form | Helically formed, continuously interlocked metal strip |
Standards
| Standards | UL 1 (Flexible Metal Conduit); CSA 22.2 No. 56; NFPA 70 (NEC) Article 348 |
|---|
Southwire 55091907 Applications
- Serves as a metal raceway for wires and cables per NEC (ANSI/NFPA-70) Article 348, in concealed or exposed installations per NEC 348 and the applicable NEC provisions.
- Carries power and lighting branch-circuit conductors and cables that connect receptacles, luminaires, equipment and office partitions, along with motor feeder, branch and control circuit conductors.
- Accepts Class 1, Class 2 and Class 3 remote-control, signaling and power-limited circuit conductors, power-limited or non-power-limited fire alarm circuit conductors, and voice, data, communications and video cables including CATV and optical fiber.
- Used for environmental air-handling spaces per NEC 300.22(C), elevators, hoistways and escalators per NEC 620.21, and cranes and hoists per NEC 610.11(C).
- Connects listed wired fixtures per NEC 410.77(C) and information technology equipment under raised floors per NEC 645.5(D)(2) and 645.5(D).
- Feeds electric signs and outline lighting per NEC 600.7, 600.31 (1000 volts or less) and 600.32 (>1000 volts).
- Can act as a grounding conductor for lengths up to 6 feet (20A max) as per NEC 250.118(5).
- Class 1, Div. 2, for flexible connectors only per NEC 501.10(B)(2) & 501.30(B).
- Part of UL 1, 2, & 3 Hour Through-Penetration Firestop Systems C-AJ-1462, C-AJ-1463, C-AJ-1464, W-L-1308 and W-L-1309.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.