Southwire 55094401, Ultratite Nonmetallic Flexible Conduit 1 Inch Gray
Description
Southwire 55094401 is Ultratite® flexible nonmetallic conduit in the 1" trade size, gray. Rigid PVC reinforcement embedded in a flexible PVC wall gives it strong impact and crush resistance while keeping it highly flexible, and the conduit resists oils, mild acids and sunlight exposure.
Southwire 55094401 Technical Specs
Dimensions
| Trade Size | 1" |
|---|---|
| Inside Diameter | 1.041 in (2.64 cm) |
| Outside Diameter (approx.) | 1.290 in (3.28 cm) |
| Minimum Bend Radius | 6.0 in (15.24 cm) |
| Weight (approx.) | 26 lbs/1000 ft (39 kg/km) |
Construction
| Material | Flexible PVC wall with rigid PVC reinforcement |
|---|---|
| Color | Gray |
Ratings & Standards
| Temperature Range | -30°C to 80°C; 60°C oil (-22°F to +176°F; 140°F oil) |
|---|---|
| Standards | UL 1660; NFPA 70 (NEC) Article 356 |
Southwire 55094401 Applications
- Installs and protects electrical conductors, including motor feeder, branch and control circuit conductors and motor leads per NEC 430.145(B), for containment of 600 volt and lower potential circuits.
- Where installation, operation or maintenance calls for flexibility or protection from liquids, vapors, solids or weather, exposed or concealed, and where runs need movement, crossover connections or tight bends.
- Agricultural buildings per NEC 547.5, and industrial and commercial connections to conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment.
- Suitable for direct burial and for encasement in concrete.
- Flexible connections to swimming pool, spa and hot tub motors per NEC 680.21(A)(3) & 680.42(A)(1); electric sign and outline lighting supply and secondary-circuit conductors per NEC 600.7, 600.31 (1000 volts or less) & 600.32 (over 1000 volts).
- Floating building feeders and services per NEC 553.7, boatyards and marinas per NEC 555.13, cranes and hoists per NEC 610.11(C), and elevators, dumbwaiters, escalators, moving walks, wheelchair lifts and stairway chair lifts per NEC 620.21 (where expressly permitted).
- Under raised floors for information technology equipment conductors and cables per NEC 645.5 (D) & 645.5(D)(2); service entrance in lengths up to six feet per NEC 230.43(15).
- Approved for use in lengths longer than 6 feet per NEC 356.10(5).
- Class I, Div. 2 per NEC 501.10(B)(2); Class II, Div. 1 per NEC 502.10(A)(2); Class II, Div. 2 per NEC 502.10(B)(2); Class III, Div. 1 per NEC 503.10(A)(2); Class III, Div. 2 per NEC 503.10(B).
- Seals out water, liquids, abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated fixed alkalines, petroleum oils, salt air and spray, and weather, with a smooth interior for easy wire pulling.