Southwire 55152699, Armored Cable 350 KCMIL 3C Copper 2400 V
Southwire · MPN 55152699
Description
Southwire 55152699 is a 350 KCMIL, three-conductor non-shielded medium-voltage armored cable rated 2400 V at 100% insulation level. Its 37-strand compressed bare copper conductors carry a semi-conducting conductor shield and 90 mils of ethylene propylene rubber (EPR), with one 2 AWG bare copper grounding conductor. Aluminum interlocked armor (AIA) and a polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 55152699 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | Ethylene propylene rubber (EPR) |
| Insulation Thickness | 90 mils (2.29 mm) |
| Diameter Over Insulation | 0.865 in (2.20 cm) |
Shielding & Grounding
| Shielding | Non-shielded |
|---|---|
| Grounding Conductor | One 2 AWG Class B compressed stranded bare copper |
Armor & Jacket
| Filler | Wax paper |
|---|---|
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.183 in (5.54 cm) |
| Outer Jacket | Polyvinyl chloride (PVC) |
| Jacket Thickness | 80 mils (2.03 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.349 in (5.97 cm) |
|---|---|
| Approximate Weight | 4805 lbs/1000 ft (7151 kg/km) |
| Maximum Pull Tension | 8400 lbs (3810.17 kg) |
| Minimum Bend Radius | 16.4 in (41.66 cm) |
Ratings
| Voltage Rating | 2400 V |
|---|---|
| Conductor Temperature | 105°C normal operation; 130°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Location Rating | Class I and II, Division 2 per NEC Article 501 and 502 |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
It is made in America and compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661.
Southwire 55152699 Applications
- Wet and dry areas, conduits, ducts, troughs and trays.
- Direct burial.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.