Southwire 55173002, Metal Clad Cable 10 AWG 3C with Ground Solid Copper THHN 600 V Steel Armor
Description
Southwire 55173002 is a Duraclad® Type MC cable with three 10 AWG solid copper THHN/THWN conductors, black, white and red, and a green insulated ground conductor, under light weight galvanized steel interlocked armor. It is rated 600 V, and its conductors are rated 90°C dry.
Southwire 55173002 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Number of Conductors | 3, plus a grounding conductor |
| Conductor Construction | Solid copper per ASTM B3 |
| Stranding | Solid |
| Conductor Colors | Black, White, Red |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.101 in (0.26 cm) |
Grounding and Armor
| Grounding Conductor | Green polyvinyl chloride with nylon sheath Type THHN/THWN insulated ground conductor |
|---|---|
| Ground Size | 1x10 |
| Binder | Mylar tape with print legend wrapped around the assembly |
| Armor | Light weight galvanized steel interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.593 in (1.51 cm) |
|---|---|
| Approximate Weight | 253 lbs per 1,000 ft (377 kg/km) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Temperature Rating | 90°C dry, Type THHN/THWN conductors |
| Location | Dry, indoor locations only (unjacketed Type MC) per NEC 330.10(A)(10) |
| Anti-Short Bushing | Not required |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Also Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 55173002 Applications
- Power distribution on branch and service circuits in commercial, industrial, institutional and multi-residential buildings.
- Fished installations, or embedded in plaster.
- Exposed or concealed runs.
- Environmental air-handling spaces under NEC 300.22(C).
- Places of assembly (NEC 518.4) and theaters (NEC 520.5).
- Cable tray and approved raceways.
- Under raised floors, for information technology equipment wiring under NEC Article 645.
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.