Southwire 55208099, Medium Voltage Cable 350 KCMIL Copper 15 kV Black PVC
Description
Southwire 55208099 is a shielded single-conductor medium voltage power cable, rated 15 kV at the 100% insulation level, with a 350 KCMIL Class B compressed stranded bare copper conductor of 37 strands and a black SIMpull PVC jacket. The conductor carries 175 mils of NL-EPR insulation between a semi-conducting conductor shield and a strippable semi-conducting insulation shield, under a helically wrapped 5 mil copper tape shield with 25% overlap. Conductor temperature is 105°C continuous.
Southwire 55208099 Technical Specs
Construction
| Number of Conductors | 1 |
|---|---|
| Conductor Size | 350 KCMIL |
| Strands | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | No Lead Ethylene Propylene Rubber (NL-EPR) |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape with 25% overlap |
| Jacket | SIMpull Polyvinyl Chloride (PVC) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor | 0.661 in (1.68 cm) |
|---|---|
| Diameter Over Insulation | 1.037 in (2.63 cm) |
| Insulation Thickness | 175 mils (4.45 mm) |
| Diameter Over Shield | 1.097 in (2.79 cm) |
| Jacket Thickness | 80 mils (2.03 mm) |
| Overall Diameter (approx.) | 1.277 in (3.24 cm) |
| Weight (approx.) | 1,661 lbs/1000 ft (2,472 kg/km) |
Installation Limits
| Maximum Pulling Tension | 2,800 lbs (1,270.06 kg) |
|---|---|
| Minimum Bending Radius | 15.3 in (38.86 cm) |
Ratings
| Voltage Rating | 15 kV |
|---|---|
| Insulation Level | 100% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lb/ft |
Rated at -25°C for cold bend and cold impact, and marked LTDD, when CSA listed or dual UL/CSA listed.
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 | FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger) |
| CSA C22.2 No. 2556 / UL 2556 | Cable Test Methods |
| CSA C68.10 | Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| ICEA S-97-682 | Standard for Shielded Utility Cable Rated for 5 - 46kV |
| IEEE 1202 | FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger) |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 55208099 Applications
- Wet and dry locations, and installation in conduits, ducts, troughs and trays.
- Direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5).
- Pulls into conduit without the aid of lubrication: the PVC jacket is made with SIM technology and has a coefficient of friction (COF) of 0.2.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.