Southwire 55259889, Armored Cable 500 KCMIL 3C Copper XHHW-2 600 V
Southwire · MPN 55259889
Description
Southwire 55259889 is a 500 KCMIL, three-conductor armored cable rated 600 V. Its 37-strand compressed bare copper conductors carry 65 mils of XHHW-2 cross-linked polyethylene (XLPE) insulation, with three 1 AWG bare copper ground wires, one in each interstice, whose combined area is 50% of the phase conductor. Aluminum interlocked armor (AIA) and a polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 55259889 Technical Specs
Conductors & Insulation
| Conductor Size | 500 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Diameter Over Conductor | 0.789 in (2.00 cm) |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 65 mils (1.65 mm) |
| Conductor Colors | Black |
Grounding, Armor & Jacket
| Grounding Conductors | Three 1 AWG bare copper ground wires, one in each interstice between conductors; combined circular mil area 50% of the phase conductor |
|---|---|
| Filler | Paper |
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.275 in (5.78 cm) |
| Outer Jacket | Polyvinyl chloride (PVC) |
| Jacket Thickness | 75 mils (1.91 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.425 in (6.16 cm) |
|---|---|
| Approximate Weight | 6629 lbs/1000 ft (9865 kg/km) |
| Maximum Pull Tension | 12000 lbs (5443.10 kg) |
| Minimum Bend Radius | 17.0 in (43.18 cm) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Location Rating | Class I, II, and III, Division 2 per NEC Article 501 and 502 |
| Silicone Free | Yes |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1569 Metal-Clad Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
Southwire 55259889 Applications
- Wet and dry areas, conduits, ducts, troughs and trays.
- Direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.