Southwire 55337103, Type AC Armored Cable 8 AWG 4C Stranded Copper THHN Steel Armor
Description
Southwire 55337103 is a Duraclad® Type AC armored cable with four 8 AWG 19-strand copper THHN/THWN conductors, black, white, red and blue, with a moisture-resistant, flame-retardant paper covering, under galvanized steel interlocking armor with a 16 AWG aluminum bond wire. For dry locations only; anti-short bushings are required.
Southwire 55337103 Technical Specs
Conductors and Insulation
| Conductor Size | 8 AWG |
|---|---|
| Number of Conductors | 4 |
| Conductor | 19-strand combination unilay stranded copper per ASTM B3 and B787 |
| Stranding | 19 strands |
| Conductor Colors | Black, White, Red, Blue |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 35 mils (0.89 mm) |
| Diameter Over Conductor | 0.143 in (0.36 cm) |
Bonding and Armor
| Bond Wire | Solid 16 AWG aluminum per ASTM B800 |
|---|---|
| Binder | Moisture-resistant, flame-retardant paper covering |
| Armor | Galvanized steel interlocking armor |
Dimensions and Weight
| Diameter Over Armor | 0.888 in (2.26 cm) |
|---|---|
| Approximate Weight | 635 lbs per 1,000 ft (945 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
|---|---|
| Location | Dry locations only |
| Anti-Short Bushings | Required |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B787 | 19 Wire Combination Unilay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 4 | Armored Cables |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | A-A59544 (formerly J-C-30B) |
| National Electrical Code | NFPA 70, Article 320 |
Southwire 55337103 Applications
- Branch and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22(C).
- Cable tray and approved raceways.
- Under raised floors, for information technology equipment conductors and cables per NEC Article 645.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.