Southwire 55388008, Building Wire 3/0 AWG 1C Copper XHHW-2/RW90 White
Description
Southwire 55388008 is a 3/0 AWG single-conductor copper building wire, Type XHHW-2/RW90, finished in white SIMpull insulation. Its 19 strands of Class B compressed bare copper (ASTM B3 and B8) sit under a flame-retardant, moisture-resistant thermoset cross-linked polyethylene (XLPE) wall made with Southwire's patented SIMpull Technology. XHHW-2 is rated 600 volts, or 1000 volts for sizes 8 and larger, and RW90 at 600 volts.
Southwire 55388008 Technical Specs
Conductor
| Conductor Size | 3/0 AWG |
|---|---|
| Metric Size | 85 mm² |
| Number of Conductors | 1 |
| Conductor Material | Class B compressed stranded bare copper |
| Strand Count | 19 |
| Diameter Over Conductor | 0.456 in (1.16 cm) |
Insulation
| Type | XHHW-2/RW90 |
|---|---|
| Material | Thermoset cross-linked polyethylene (XLPE), flame-retardant and moisture-resistant |
| Color | White |
| Thickness | 55 mils (1.40 mm) |
Dimensions & Weight
| Approx. Outside Diameter | 0.574 in (1.46 cm) |
|---|---|
| Approx. Weight | 564 lbs/1000 ft (839 kg/km) |
| Copper Content | 518 lbs/1000 ft (771 kg/km) |
Ratings & Compliance
| Max. Conductor Temperature | 90°C, wet or dry locations |
|---|---|
| Standards | ASTM B3, ASTM B8, ASTM B787, UL 44, UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger), CSA C22.2 No. 38, ICEA S-95-658 (NEMA WC70), Federal Specification A-A-59544, NMX-J-451-ANCE, NOM-063-SCFI |
Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661; and NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable.
Southwire 55388008 Applications
- Services, feeders and branch-circuit runs pulled through conduit, cable tray or other recognized raceways.
- Designed to be installed without pulling lubricant.
- In health care facilities, Type XHHW-2 is suitable per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 may be specified.
- Under the Canadian Electrical Code, RW90 may serve open wiring, including open wiring exposed to the weather, and raceways other than cable troughs and ventilated flexible cableways, in dry or wet locations.
- Features: sunlight resistant; -40°C cold bend; FT1; Gasoline and Oil Resistant II; CT Rated (1/0 AWG and larger); RoHS/REACH compliant.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.