Southwire 55510303, Metal Clad Cable 12 AWG 2C with Ground Solid Copper THHN
Description
Southwire 55510303 is an MC-AP™ all purpose Type MC cable with two 12 AWG solid copper conductors, insulated Type THHN/THWN in black and white, and a full-sized bare 8000 series aluminum grounding/bonding conductor, all under aluminum interlocked armor. The armor and the bare aluminum conductor together form the equipment ground path, and the conductors are rated 90°C dry.
Southwire 55510303 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 2, plus a bare aluminum grounding/bonding conductor |
| Conductor | Solid copper |
| Conductor Colors | Black, White |
| Insulation | PVC with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
Grounding and Armor
| Grounding | Full-sized bare 8000 series aluminum grounding/bonding conductor; the armor and the bare aluminum conductor together form the equipment ground path |
|---|---|
| Binder | Mylar tape, with a print legend wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.487 in (1.24 cm) |
|---|---|
| Approximate Weight | 92 lbs per 1,000 ft (137 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
|---|
Standards
| ASTM B3 | Soft or annealed copper wire |
|---|---|
| UL 83 | Thermoplastic insulated wires and cables |
| UL 1569 | Metal-clad cables |
| UL 1479 | Fire tests of penetration firestops |
| UL 1685 FT4 | Vertical-tray fire propagation and smoke release test |
| IEEE 1202 FT4 | Flame test (70,000) BTU/hr vertical tray test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 55510303 Applications
- Branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fishing through or embedding in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.